Plan Review Notes
Plan Review Notes For Permit 17081012
Permit Number 17081012
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-28 18:13:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. AS THIS IS A THRESHOLD BUILDING (6 STORY), A
 THRESHOLD INSPECTION PLAN PREPARED BY SEOR IS REQUIRED.
 REVISE THE INDEX PAGE TO INCLUDE THE THRESHOLD
 INSPECTION PLAN (SHEET 1.1, SHOWN ON INDEX AS "NOTES").
  
 2. AS THIS IS A THRESHOLD BUILDING, THREE SETS OF PLANS
 REQUIRED (CITY, SI, JOB).
  
 3. STRUCTURAL CALCS PREPARED WITH ENERCALC REFER TO
 INCORRECT (OUTDATED) CODE AND STANDARD REFERENCES, FBC
 CHAPTER 35. REVISE AND CHECK ALL.
  
 4. S2.6 SPECS A 3'6" PARAPET; CALCULATIONS (ENERCALC)
 SPEC A 5' PARAPET, CLARIFY. S2.6 SHOULD BE REMOVED
 (ROOF PLAN; NOT NEEDED FOR THIS PERMIT, SEE COMMENT
 #5), BUT CALCULATIONS SHOULD BE CONSISTENT WITH
 BUILDING DESIGN.
  
 5. PLANS HAVE TOO MUCH INFORMATION. THIS APPEARS TO BE
 A FULL SET OF PLANS, WHICH IS IN CONFLICT WITH THE
 APPLICATION (FOUNDATION ONLY). FOR FOUNDATION PERMIT,
 ONLY THE FOLLOWING IS REQUIRED:
  
 PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION
 PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB)
 GEOTECHNICAL REPORT
 SURVEY DRAWING
 STORM WATER POLLUTION PREVENTION PLAN
 SITE PLAN
 1ST FLOOR ARCHITECTURAL PLAN
 ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING
 FOUNDATION PLAN
 FOUNDATION DETAILS AND CROSS SECTIONS
 STRUCTURAL ENGINEER'S GENERAL NOTES
 UNDERGROUND PLUMBING PLAN (IF APPLICABLE)
 ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT (IF
 APPLICABLE)
 ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR
 EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT).
 IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT,
 AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR
 PLAN SHOWING UNDERGROUND FIRE LINE
 THRESHOLD INSPECTION PLAN OR RESIDENT INSPECTION PLAN
 (AS APPLICABLE)
 INFORMATION SPECIFICALLY REQUESTED BY FIRE OR
 ENGINEERING
  
 SUBMISSION OF THE SHEETS NOT REQUIRED DELAYS FOUNDATION
 PERMIT ISSUANCE. A REVIEW HAS NOT BEEN DONE ON SHEETS
 OTHER THAN THOSE ABOVE. PLEASE REMOVE SHEETS NOT LISTED
 ABOVE.
  
 6. PLEASE ADVISE, WHO WILL PERFORM THE SOILS
 IMPROVEMENT MONITORING? THIS INFORMATION MAY BE
 PROVIDED IN A LETTER, ON LETTERHEAD, FBC 107. IF THE
 VIBROFLOTATION PERMIT HAS BEEN ISSUED BEFORE THE
 FOUNDATION PERMIT IS RESUBMITTED, YOU MAY DISREGARD
 THIS COMMENT. UPON ISSUANCE, ALL DOCUMENTS ASSOCIATED
 WITH A PERMIT BECOME AN OFFICIAL RECORD.
  
 7. I WAS UNABLE TO LOCATE THE THRESHOLD STATEMENT
 REQUIRED BY FS 553.79(7)(D) ON THE ARCHITECT'S AND
 ENGINEER'S PLAN. REVISE TO INCLUDE. IF THIS IS ALREADY
 ON THE PLANS, PLEASE ADVISE AS TO LOCATION AND IT IS
 POSSIBLE THAT THIS REVIEW CAN BE PASSED WITH PROVISO.
  
 8. PLEASE ADVISE, WILL THIS FOUNDATION PERMIT BE A
 PRIVATE PROVIDER PROJECT? IF YES, PLEASE PROVIDE
 PAPERWORK.
  
  
  
  