| 2017-08-24 16:30:37 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF A ROOF DIAGRAM THAT SHOWS THE | | | LOCATIONS OF THE SKYLIGHTS THAT ARE BEING REPLACED. | | | SPECIFY THE ROOF SLOPE AND THE ROOF HEIGHT ON THE | | | DRAWINGS. THE DESIGN PRESSURES FROM THE PRODUCT | | | APPROVALS IS +60 PSF AND - 60 PSF, WHICH IS NOT | | | ADEQUATE FOR ROOF ZONE 3. FBC 107.2.1 | | | | | | |
|