2017-11-14 07:52:072014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080987
 W. P. B. PERMIT: 15100589
 ADD: 1600 N. DIXIE HWY.
 CONT: R J S CONSTRUCTION
 TEL: 561-795-4712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 13/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE FROM THE ISSUED PERMIT THERE HAS BEEN A
 CHANGE IN DESIGN PROFESSIONALS. UNDER THE PERMIT ISSUED
 15100589 THE ARCHITECT WAS NIKI L. NORTON AR 91827,
 UNDER THIS REVISION ARCHITECT VLAD DUMITRESCU AR 93102
 IS SHOWN AS THE ARCHITECT OF RECORD. PLEASE SHOW
 COMPLIANCE WITH THE:
  
 FLORIDA ADMINISTRATIVE CODE 61G-18.002(2) PRIOR TO
 SEALING, SIGNING AND DATING WORK, A SUCCESSOR
 REGISTERED ARCHITECT SHALL BE REQUIRED TO NOTIFY THE
 ORIGINAL REGISTERED ARCHITECT, HIS SUCCESSORS, OR
 ASSIGNS BY CERTIFIED LETTER TO THE LAST KNOWN ADDRESS
 OF THE ORIGINAL REGISTERED ARCHITECT OF THE SUCCESSOR'S
 INTENTION TO USE OR REUSE THE ORIGINAL REGISTERED
 ARCHITECT'S WORK. THE SUCCESSOR REGISTERED ARCHITECT
 WILL TAKE FULL RESPONSIBILITY FOR THE DRAWING AS THOUGH
 THEY WERE THE SUCCESSOR REGISTERED ARCHITECT'S ORIGINAL
 PRODUCT.
  
 2) THE ORIGINAL BUILDING DESIGN WAS LISTED AS A III-B
 UNSPRINKLERED BUILDING, THE NEW BUILDING DESIGN BY THE
 NEW ARCHITECT IS A V-B. THE COVERSHEET A-0 INDICATES
 THE BUILDING IS TO BE FIRE SPRINKLERED, THE WHOLE
 BUILDING OR ONLY THIS TENANT SPACE. NO FIRE SPRINKLER
 PLANS WERE SUBMITTED UNDER THIS REVIEW.107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) THE COVER SHEET INDICATES THIS IS TO BE A BUSINESS
 OCCUPANCY BUT THE FLOOR PLAN INDICATES A SQUARE FOOT
 AREA OF 1309 SQ. FT. OF SALES/ RECEPTION WITH AN
 OCCUPANT LOAD OF 13. PLEASE EXPLAIN WHY THIS AREA IS
 NOT A MERCANTILE OCCUPANCY SINCE IT IS A SALES FLOOR?
 107.2.1.3. THE OTHER ISSUE IN EITHER CASE OCCUPANT
 LOADS ARE NEVER ROUNDED DOWN YOU ALWAYS HAVE OCCUPANTS
 AS WHOLE PEOPLE. THE
  
 4) SHEET A-1 ACCESSIBLE DETAILS:
 4A) THE RESTROOM (WATER CLOSET) GRAB BARS SHOW THE
 DIMENSION FROM THE FINISH FLOOR TO THE CENTERLINE OF
 THE GRAB BAR, PLEASE NOTE UNDER THE 2014
 FBC-ACCESSIBILITY CODE THE DIMENSIONS ARE TAKEN FROM
 THE FINISH FLOOR TO THE TOP OF THE GRASPABLE SURFACE
 THIS WILL MAKE A ? INCH DIFFERENCE IN HEIGHT.
  
 ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 4B) THE ACCESSIBLE DETAIL UPPER LEFT PORTION OF THE
 SHEET SHOWS THE MAXIMUM HEIGHT OF THE MIRROR TO BE 40
 INCHES DRAWN TO THE BOTTOM EDGE OF THE MIRROR, PLEASE
 NOTE THE 40 INCHES MAXIMUM HEIGHT IS TO BE TAKEN FROM
 FINISH FLOOR TO THE BOTTOM EDGE OF THE REFLECTIVE
 MIRROR FINISH SEE ACCESSIBILITY CODE 603.3.
  
 4C) PLEASE NOTE THE HANDICAPPED SIGNAGE WITH TACTILE
 SURFACE IS INDICATED TO BE 5 FEET CANTERED ABOVE THE
 FINISH FLOOR. PLEASE ALSO REVIEW SECTION SIGNAGE.
 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND. TACTILE
 CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES MINIMUM
 ABOVE THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM
 THE BASELINE OF THE LOWEST TACTILE CHARACTER AND 60
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE HIGHEST
 TACTILE CHARACTER.
  
 4D) DETAIL # 3 THE LOUNGE ELEVATION SHOWS A MICROWAVE
 THE BOTTOM AT APPROXIMATELY 4 FOOT 6 INCHES ABOVE
 FINISH FLOOR.
 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 (22.2 N) MAXIMUM.
  
 4E) THE DETAIL # 3 ALSO SHOWS THERE TO BE A SINK IN THE
 LOUNGE AREA BUT THE ELEVATION DETAIL DOES NOT PROVIDE A
 VERTICAL DIMENSION FOR THE SINK ELEVATION. 2014
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  