2017-11-17 17:09:221ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH THE WATER CLOSET SHALL BE
 POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO
 ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION. PER FBC ACC 604.2
  
 2. THE GRAB BARS SHALL BE MEASURE FROM FINISHED FLOOR
 TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. FBC ACC 604.7
  
 4. THE LOUNGE SINK SHALL COMPY WITH FBC ACC 606.2 CLEAR
 FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5. A GREASE TRAP IS REQUIRED ON KITCHEN SINK ONLY. PER
 FBC PL 1003.3.1
  
 6. WHERE FOOD WASTE GRINDERS CONNECT TO GREASE
 INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE
 DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR.
 SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE
 SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE
 GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA
 SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER. PER
 FBC PL 1003.3.2
  
 7. ON SHT A-4 THE SANITARY AND WATER RISER DIAGRAMS ARE
 LABELED INCORRECTLY PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 8. BRANCH DRAIN FROM KITCHEN SHALL CONNECT TO BUILDING
 DRAIN DOWN STREAM OF BATHROOM GROUP. PER FBC PL 912.1
  
 9. HORIZONTAL DRY VENTS ARE PROHIBITED THE WENTS ON THE
 MOP SINK AND MENS WC SHALL COMPLY WITH FBC PL 905.3,
 905.4
  
 10. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 11. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 TANKLESS HEATER AND THE GREASE TRAP. PER WPB AMEND TO
 FBC 107.2.1
  
 12. PLEASE PROVIDE SIZING CALCULATIONS FOR GREASE TRAP.
 PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  