| 2017-11-16 13:01:34 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED |
| | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | 2. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| | AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2 |
| | 3. MECHANICAL SHEET SHOWS THE RTU'S AS 208 VOLT, BUT |
| | PANEL SCHEDULE SHOWS THE WIRING AS 120 VOLT. PROVIDE |
| | CORRECTION. FBC 107.2.1; NEC 408.4 |
| | 4. TWO OF THE RTU'S ON POWER PLAN ARE MARKED AS RTU-2. |
| | PROVIDE CORRECTION. FBC 107.2.1 |
| | 5. WIRE SIZE FROM GUTTER TO METER CAN IS SHOWN AS # 3. |
| | THIS SIZE WIRE IS NOT RATED FOR 200 AMPS. PROVIDE |
| | CORRECTION. NEC 310.15(B)(16) |
| | 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94 |
| | 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 9. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| | 8.4.2. FBC CE 405.7.1 |
| | 10. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 |
| | 11. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER. WITH |
| | INFORMATION PROVIDED, IT APPEARS THE CIRCUIT TO THIS |
| | UNIT IS UNDERSIZED. 13,500 WATTS/208 VOLTS = 64.9 AMPS. |
| | A 60 AMP CIRCUIT IS SHOWN IN PANEL SCHEDULE. NEC 110.3, |
| | 215.2, 310.15(B)(16) |
| | 12. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT ON ROOF PER CODE. NEC 210.63 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |