| Plan Review Notes For Permit 17080980 |
| Permit Number |
17080980 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-15 14:58:32 | 9/15/17 PLUMBING 1ST REVIEW DENIED | | | | | | 1) VALUE OF JOB COST SEEMS LOW AND LOOKS TO HAVE BEEN | | | MODIFIED AFTER THE OWNER AND CONTRACTOR SIGNED. PROVIDE | | | A BONA FIDE SIGNED CONTRACT SHOWING AMOUNT FBC 109.3 | | | | | | 2) CITY RECORDS DOES NOT INDICATE A PERMIT BEING ISSUED | | | FOR REPLACEMENT OF ANY WATER HEATERS OR TANKLESS WATER | | | HEATERS INCLUDING THE REQUIRED ELECTRIC FOR ONE AS | | | WELL. EXISTING TANKLESS IS UNDERSIZED AND WITH THE HEAT | | | RAISED BASED ON 32 DEGREES INCREASE TO GET HOT WATER OF | | | 111 DEGREES REQUIRED IT WOULD NOT COMPLY WITH 607.1 AND | | | 604.3 FBC-PLUMBING . PLEASE INCLUDE A CORRECTLY SIZED | | | WATER HEATER IN YOUR PLANS REVISE P-1 ELECTRIC WATER | | | HEATER SCHEDULE TO SHOW CORRECT INFORMATION. AS YOU CAN | | | SEE FROM THE CHART BELOW A 32 DEGREE HEAT RAISE WOULD | | | GET YOU 111 DEGREE WATER WHICH WILL GIVE YOU ENOUGH HOT | | | WATER FOR 1 FIXTURE ONLY. | | | | | | TITAN N-120 TEMPERATURE RISE CHART (? FAHRENHEIT) ABOVE | | | YOUR AMBIENT TEMPERATURE | | | FLOW RATE 1.0 GPM 1.5 GPM 2.0 GPM 2.5 GPM 3.0 GPM 3.5 | | | GPM 4.0 GPM | | | TEMP RISE 81? 54? 40? 32? 27? 23? 20? | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|