Plan Review Notes For Permit 17080883
Permit Number 17080883
Review Stop P
Sequence Number 3
Notes
Date Text
2018-01-12 14:15:362ND REVIEW: FBC 2014 5TH EDITION
  
 PROVISO
  
 1. THE WATER FOUNTAIN SHALL HAVE TWO SPOUTS ONE FOR A
 PERSON IN A WHEEL CHAIR AND ONE FOR A STANDING PERSON.
 PER FBC ACC 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 602.4 SPOUT HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 SHALL COMPLY BEFORE FINAL INSPECTION.
  
  