| 2018-01-11 09:32:35 | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE WATER FOUNTAIN SHALL HAVE TWO SPOUTS ONE FOR A | | | PERSON IN A WHEEL CHAIR AND ONE FOR A STANDING PERSON. | | | PER FBC ACC 211.2 MINIMUM NUMBER. | | | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | | 602.7. | | | 602.4 SPOUT HEIGHT. | | | SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE | | | THE FINISH FLOOR OR GROUND. | | | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. | | | SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING | | | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 | | | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|