Plan Review Notes
Plan Review Notes For Permit 17080883
Permit Number 17080883
Review Stop M
Sequence Number 2
Notes
Date Text
2017-12-19 17:01:562ND REVIEW FBC-2014 MECHANICAL , FBC-14 ENERGY
 CONSERVATION CODE
 PERMIT #17080883
 12/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE REQUIRED AUTOMATICALLY CONTROLLED
 SHUTOFF DAMPERS FOR THE O/A DUCTS TO AHU 2 & 3 ARE NOT
 SHOWN. PLEASE NOTE THAT BOTH AIR HANDLERS MUST BE
 EQUIPPED WITH THE DAMPERS- SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION
  
 2) SHEETS A-1.0, M-1, M-2: SHOW ON THE PLANS THE A-3
 AREA AND ADJUST THE O/A CALCULATION FOR THAT SPACE IN
 ACCORDANCE WITH TABLE 403.3.
  
 3) ONE SET OF AC CALCULATIONS IS MISSING FROM THE
 RESUBMITTAL PACKAGE- PLEASE PROVIDE THE MISSING SET.
  