| Plan Review Notes For Permit 17080883 |
| Permit Number |
17080883 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-12-19 17:01:56 | 2ND REVIEW FBC-2014 MECHANICAL , FBC-14 ENERGY | | | CONSERVATION CODE | | | PERMIT #17080883 | | | 12/19/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: THE REQUIRED AUTOMATICALLY CONTROLLED | | | SHUTOFF DAMPERS FOR THE O/A DUCTS TO AHU 2 & 3 ARE NOT | | | SHOWN. PLEASE NOTE THAT BOTH AIR HANDLERS MUST BE | | | EQUIPPED WITH THE DAMPERS- SECTION C403.2.4.4 FBC-14 | | | ENERGY CONSERVATION | | | | | | 2) SHEETS A-1.0, M-1, M-2: SHOW ON THE PLANS THE A-3 | | | AREA AND ADJUST THE O/A CALCULATION FOR THAT SPACE IN | | | ACCORDANCE WITH TABLE 403.3. | | | | | | 3) ONE SET OF AC CALCULATIONS IS MISSING FROM THE | | | RESUBMITTAL PACKAGE- PLEASE PROVIDE THE MISSING SET. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|