| Plan Review Notes For Permit 17080883 |
| Permit Number |
17080883 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-01-12 15:54:02 | ****PROVISOS**** | | | ****ISSUED AT APPLICANT'S RISK**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE PARKING LOT WAS INSTALLED WITHOUT A PERMIT, | | | APPLY AT THIS TIME. AN ACCESSIBLE ROUTE IS REQUIRED AND | | | WILL BE REVIEWED UNDER THE PARKING LOT PERMIT. | | | | | | 2. UNABLE TO LOCATE OCCUPANT LOAD FOR THE BUSINESS | | | SPACES, REVISE PLAN TO INCLUDE, FBC B 1004. | | | | | | 3. NO EXTERIOR LIGHTING SHOWN ON THE ENERGY CALC INPUT | | | REPORT; MEANS OF EGRESS ILLUMINATION IS REQUIRED. | | | CONFIRM THAT ALL ITEMS REQUIRED TO BE ON THE ENERGY | | | CALC ARE INCLUDED. | | | | | | RESPONSE IS THAT THERE IS NO EXTERIOR ILLUMINATION. | | | THIS IS REQUIRED, FBC B 1006.1. REVISE PLAN AND ENERGY | | | CALCS ACCORDINGLY, OR SEND EMAIL TO EXPLAIN HOW THIS | | | REQUIREMENT WILL BE MET. | | | | | | 4. A ROOF PRODUCT APPROVAL WAS PROVIDED, ASSEMBLY | | | SELECTED WITH A DP LIMITATION OF -52.5. RAS117 | | | CALCULATIONS PREPARED BY A DESIGN PROFESSIONAL IS | | | REQUIRED PRIOR TO ISSUANCE OF ROOF SUB PERMIT. THIS MAY | | | BE SUBMITTED AT TIME OF ROOF PERMIT APPLICATION. | | | |
|