Plan Review Notes
Plan Review Notes For Permit 17080883
Permit Number 17080883
Review Stop B
Sequence Number 2
Notes
Date Text
2018-01-12 15:54:02****PROVISOS****
 ****ISSUED AT APPLICANT'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE PARKING LOT WAS INSTALLED WITHOUT A PERMIT,
 APPLY AT THIS TIME. AN ACCESSIBLE ROUTE IS REQUIRED AND
 WILL BE REVIEWED UNDER THE PARKING LOT PERMIT.
  
 2. UNABLE TO LOCATE OCCUPANT LOAD FOR THE BUSINESS
 SPACES, REVISE PLAN TO INCLUDE, FBC B 1004.
  
 3. NO EXTERIOR LIGHTING SHOWN ON THE ENERGY CALC INPUT
 REPORT; MEANS OF EGRESS ILLUMINATION IS REQUIRED.
 CONFIRM THAT ALL ITEMS REQUIRED TO BE ON THE ENERGY
 CALC ARE INCLUDED.
  
 RESPONSE IS THAT THERE IS NO EXTERIOR ILLUMINATION.
 THIS IS REQUIRED, FBC B 1006.1. REVISE PLAN AND ENERGY
 CALCS ACCORDINGLY, OR SEND EMAIL TO EXPLAIN HOW THIS
 REQUIREMENT WILL BE MET.
  
 4. A ROOF PRODUCT APPROVAL WAS PROVIDED, ASSEMBLY
 SELECTED WITH A DP LIMITATION OF -52.5. RAS117
 CALCULATIONS PREPARED BY A DESIGN PROFESSIONAL IS
 REQUIRED PRIOR TO ISSUANCE OF ROOF SUB PERMIT. THIS MAY
 BE SUBMITTED AT TIME OF ROOF PERMIT APPLICATION.
  