2017-10-02 12:58:421ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW CLEAR FLOOR SPACE FOR TOILET ,
 LAVATORY'S, SHOWER , WATER FOUNTAIN AND BREAK ROOM
 SINK. PER FBC ACC 602.2 ,604.3.1, 606.2, 608.2.1
  
 2. TRANSFER TYPE SHOWER COMPARTMENTS SHALL COMPLY WITH
 FBC ACC 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES BY
 36 INCHES CLEAR INSIDE DIMENSIONS MEASURED AT THE
 CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 36
 INCH WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT. CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48
 INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL
 SHALL BE PROVIDED.
  
 3. IN TRANSFER TYPE SHOWER COMPARTMENTS, SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE SIDE WALL OPPOSITE THE
 SEAT 38 INCHES MINIMUM AND 48 INCHES-MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES) MAXIMUM FROM THE CENTERLINE OF THE SEAT
 TOWARD THE SHOWER OPENING. PER FBC ACC 608.5.1
  
 4. SHOW COMPLIANCE WITH FBC ACC 610.3 IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES OF THE COMPARTMENT ENTRY. THE TOP
 OF THE SEAT SHALL BE 17 INCHES MINIMUM AND 19 INCHES
 MAXIMUM ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL
 COMPLY WITH 610.3.1 OR 610.3.2.
  
 5. SHT. A2.3 DETAIL #4 CLEAR FLOOR SPACE AT TOILET THE
 DETAIL SHOWING 48" WIDE DO NOT COMPLY PLEASE REMOVE
 FROM PLAN. PER FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 6. SHT. A2.3 DETAIL #4 GRAB BARS AT WATER CLOSET (A)
 BACK WALL DOES NOT COMPLY IT SHALL COMPLY WITH FBC ACC
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 7. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE TO FINISHED FLOOR. FBC ACC 609.4
  
 8. THE CENTERLINE OF THE WATERCLOSET SHALL BE 16"-18"
 OFF SIDE WALL. PER FBC ACC 604.2
  
 9. SHT. A2.3 THE LAYOUT OF THE BREAKROOM PLAN DETAIL #5
 DOES NOT MATCH DETAIL #6 DETAIL #5 DOES NOT SHOW THE
 CABINET ON THE LEFT SIDE OF THE SINK THAT IS SHOWN ON
 DETAIL #6 PLEASE CLARIFY . PER WPB AMEND TO FBC 107.2.1
  
 10. SHOW COMPLIANCE WITH FBC ACC 608.3.1 TRANSFER TYPE
 SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES FROM THE CONTROL WALL.
  
 11. LAVATORY FAUCETS SHALL COMPLY WITH FBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 12. PLEASE SHOW TRAP PRIMERS ON ALL FLOOR DRAINS AND
 FLOOR SINK ON RISER DIAGRAM. PER WPB AMEND TO FBC
 107.2.1
  
 13. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PER FBC PL 708.3.4
  
 14. PROVIDE MANUFACTURE SPEC FOR TANKLESS WATER HEATER
 AND OIL SMART SUMP PUMP. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  