| 2017-09-22 08:53:04 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17080883 |
| | 9/22/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: INDICATE HOW OUTDOOR AIR IS BEING |
| | PROVIDED TO AHU-1 & 4- NO O/A DUCTS ARE SHOWN AT THESE |
| | LOCATIONS. |
| | |
| | 2) M-1: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF |
| | DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.4 |
| | FBC-14 ENERGY CONSERVATION. |
| | |
| | 3) M-1: PLEASE ENLARGE THE SMOKE DETECTOR SYMBOLS IN |
| | THE AHU-2 & 3 CLOSET. |
| | |
| | 4) M-1 & A2.2: THE AC CLOSET DOORS SHALL BE |
| | NON-COMBUSTIBLE IN COMPLIANCE WITH SECTION C403.2.7.2 |
| | FBC-14 ENERGY CONSERVATION AND SECTION 602 FBC-14 |
| | MECHANICAL. THE PLANS INDICATE WOOD DOORS. |
| | |
| | 5) M-1: EXHAUST VENTILATION AT A RATE OF 0.25 CFMS PER |
| | SQ. FT IS REQUIRED FOR THE LOCKER ROOMS- TABLE 403.3. |
| | |
| | 6) M-2: THE 150 MPH WIND SPEED SHOWN IN THE CU MOUNTING |
| | DETAIL IS NOT CORRECT FOR PUT REGION. PLEASE REFER TO |
| | SECTION 1609 FBC-BUILDING AND PROVIDE THE CORRECT WIND |
| | SPEED, AND CURRENT WIND DESIGN CRITERIA FOR |
| | INSTALLATION OF THE CONDENSERS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |