2017-08-23 10:39:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 2.1 - DOOR # 1 IS INDICATED TO EXIT OUT
 UNDER AN EXIT STAIR AND IS NOT INDICATED AS BEING
 RATED. PER NFPA 101 CHAPTER 7, A 1 HOUR RATED DOOR IS
 REQUIRED.
  
 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS.
 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING BY CONSTRUCTION WITH THE FIRE
 RESISTANCE RATING REQUIRED FOR ENCLOSED STAIRS WITH
 FIXED OR SELF-CLOSING OPENING PROTECTIVES, EXCEPT AS
 FOLLOWS:
  
 (4) THE FIRE RESISTANCE RATING OF A SEPARATION
 EXTENDING 10 FT (3050 MM) FROM THE STAIRS SHALL NOT BE
 REQUIRED TO EXCEED 1 HOUR WHERE OPENINGS HAVE A MINIMUM
 ?-HOUR FIRE PROTECTION RATING.
  
 PLEASE PROVIDE.
  
  
 2) SHEET A 4.1 - THE FIRST FLOOR AND ROOF TRUSS SYSTEMS
 ARE INDICATED AS LIGHWEIGHT.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
 PLEASE PROVIDE.
  
  
  
 3) SHEET FP 1 - THERE IS A REFERENCE INDICATING
 COMPLAINCE WITH NFPA 13 2007 EDITION. THE CURRENT
 EDITION OF NFPA 13 PER THE FLORIDA FIRE PREVENTION
 CODE, 5TH EDITION IS 2010.
  
 PLEASE CORRECT.
  
  
  
 4) SHEET FP 1 - THERE IS A CLOSET INDICATED ON THE
 FIRST FLOOR WITH NO DIMENSIONS AND NO SPRINKLER
 PROTECTION. THIS CLOSET IS REQUIRED TO HAVE SPRINKLER
 PROTECTION.
  
 PLEASE PROVIDE.
  
  
  
 5) SHEET FP 1 - THERE APPEARS TO BE ONE SPRINKLER
 SERVING UNDER THE STAIRS STORAGE SPACE. ANOTHER
 SPRINKLER APPEARS TO BE REQUIRED OR ADD A WALL TO LIMIT
 THE DISTANCE.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 6) SHEET A 5.1 - THERE IS REFERENCE TO THE ELEVATOR
 BEING INSTALLED PER MANUFACTURES SPEC. PER NFPA 1,
 CHAPTER 11, BUILDING SERVICES.
  
 11.3.1 FIRE FIGHTERS? EMERGENCY OPERATIONS.
 11.3.1.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS? EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS. [101:9.4.3.1]
  
 PLEAE ENSURE COMPLIANCE AND PROVIDEA AN APPLICABLE
 NOTE.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL