| 2017-08-23 10:39:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 2.1 - DOOR # 1 IS INDICATED TO EXIT OUT |
| | UNDER AN EXIT STAIR AND IS NOT INDICATED AS BEING |
| | RATED. PER NFPA 101 CHAPTER 7, A 1 HOUR RATED DOOR IS |
| | REQUIRED. |
| | |
| | 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS. |
| | 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE |
| | INTERIOR OF THE BUILDING BY CONSTRUCTION WITH THE FIRE |
| | RESISTANCE RATING REQUIRED FOR ENCLOSED STAIRS WITH |
| | FIXED OR SELF-CLOSING OPENING PROTECTIVES, EXCEPT AS |
| | FOLLOWS: |
| | |
| | (4) THE FIRE RESISTANCE RATING OF A SEPARATION |
| | EXTENDING 10 FT (3050 MM) FROM THE STAIRS SHALL NOT BE |
| | REQUIRED TO EXCEED 1 HOUR WHERE OPENINGS HAVE A MINIMUM |
| | ?-HOUR FIRE PROTECTION RATING. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | 2) SHEET A 4.1 - THE FIRST FLOOR AND ROOF TRUSS SYSTEMS |
| | ARE INDICATED AS LIGHWEIGHT. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 3) SHEET FP 1 - THERE IS A REFERENCE INDICATING |
| | COMPLAINCE WITH NFPA 13 2007 EDITION. THE CURRENT |
| | EDITION OF NFPA 13 PER THE FLORIDA FIRE PREVENTION |
| | CODE, 5TH EDITION IS 2010. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | 4) SHEET FP 1 - THERE IS A CLOSET INDICATED ON THE |
| | FIRST FLOOR WITH NO DIMENSIONS AND NO SPRINKLER |
| | PROTECTION. THIS CLOSET IS REQUIRED TO HAVE SPRINKLER |
| | PROTECTION. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 5) SHEET FP 1 - THERE APPEARS TO BE ONE SPRINKLER |
| | SERVING UNDER THE STAIRS STORAGE SPACE. ANOTHER |
| | SPRINKLER APPEARS TO BE REQUIRED OR ADD A WALL TO LIMIT |
| | THE DISTANCE. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 6) SHEET A 5.1 - THERE IS REFERENCE TO THE ELEVATOR |
| | BEING INSTALLED PER MANUFACTURES SPEC. PER NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES. |
| | |
| | 11.3.1 FIRE FIGHTERS? EMERGENCY OPERATIONS. |
| | 11.3.1.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS? EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS. [101:9.4.3.1] |
| | |
| | PLEAE ENSURE COMPLIANCE AND PROVIDEA AN APPLICABLE |
| | NOTE. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |