| 2017-09-20 10:21:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94 |
| | 2. RISER DIAGRAM SHOWS A "FUTURE PANEL C", HOWEVER, |
| | POWER PLAN SHOWS THIS INSTALLED AND CIRCUITS BEING FED |
| | FROM THIS PANEL. CLARIFY AND/OR CORRECT. FBC 107.2.1 |
| | 3. ALL KITCHEN RECEPTACLES REQUIRE GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8 |
| | 4. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 |
| | 5. OUTSIDE RECEPTACLE BY A/C EQUIPMENT REQUIRES GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. PLAN DOES NOT SHOW LIGHTING |
| | CONTROLLED BY EITHER TIME CLOCK OR OCCUPANCY SENSORS |
| | REQUIRED. FBC CE 405.2.2, 405.2.2.2 |
| | 7. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| | CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| | CODE. FBC CE 405.5 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |