2017-09-22 15:06:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC A 201.1.1, VERTICAL ACCESSIBILITY IS NOT SHOWN
 FOR THE THREE ELEVATED PLATFORM AREAS. REVISE PLAN TO
 INCLUDE OR REVISE PLAN TO CLARIFY USE OF THE AREAS,
 APPLICALBE EXCEPTION(S).
  
 2. I WAS UNABLE TO FIND A LIFE SAFETY PLAN. EITHER
 PROVIDE ONE, OR REVISE THE FLOOR PLAN TO INCLUDE
 INFORMATION (OCCUPANT LOAD AND SQUARE FOOT AREA FOR
 EACH SPACE, TRAVEL DISTANCE, COMMON PATH, DEAD ENDS,
 FBC CHAPTER 10). THE OCC LOAD FOR THE ASSEMBLY SPACE
 WAS PROVIDED, BUT IS REQUIRED FOR THE REST OF THE
 BUILDING, FBC 107.
  
 3. IT APPEARS THAT A PARKING LOT WAS INSTALLED WITHOUT
 A PERMIT, PLEASE APPLY AT THIS TIME OR PROVIDE PERMIT
 NUMBER.
  
 4. REVISE PLAN TO INCLUDE INFORMATION ABOUT THE
 MERCANTILE AREA - WHAT WILL BE SOLD AND STORED HERE?
 FBC 107. ENERGY CALCS DO NOT APPEAR TO INCLUDE A
 MERCANTILE AREA; PLEASE CORRELATE. IF THIS INFORMATION
 IS NOT AVAILABLE AT THIS TIME, REVISE PLAN TO INDICATE
 THAT FUTURE MERCANTILE TENANT BUILDOUT WILL BE UNDER
 SEPARATE PERMIT.
  
 5. WHAT IS CURRENTLY THE OCCUPANCY (OR OCCUPANCIES) FOR
 THIS BUILDING? IF THIS IS A CHANGE OF OCCUPANCY, REVISE
 PLAN TO INCLUDE THIS INFORMATION, REVISE PLAN TO SHOW
 COMPLIANCE WITH FBC EB CHAPTER 10. AN IMPACT FEE
 ASSESSMENT MAY BE REQUIRED.
  
 6. I WAS UNABLE TO LOCATE A DOOR SCHEDULE, PLEASE
 PROVIDE (INCLUDING HARDWARE SCHEDULE), FBC B 1008, FBC
 EC.
  
 7. NO DOORS ARE SHOWN ON THE ENERGY CALC INPUT REPORT,
 ARE ALL DOORS GLAZED? A HOLLOW METAL DOOR PRODUCT
 APPROVAL WAS SUBMITTED, FBC 107.
  
 8. NO EXTERIOR LIGHTING SHOWN ON THE ENERGY CALC INPUT
 REPORT; MEANS OF EGRESS ILLUMINATION IS REQUIRED.
 CONFIRM THAT ALL ITEMS REQUIRED TO BE ON THE ENERGY
 CALC ARE INCLUDED.
  
 9. A ROOF PRODUCT APPROVAL WAS PROVIDED, ASSEMBLY
 SELECTED WITH A DP LIMITATION OF -52.5. RAS117
 CALCULATIONS PREPARED BY A DESIGN PROFESSIONAL IS
 REQUIRED PRIOR TO ISSUANCE OF ROOF SUB PERMIT. THIS MAY
 BE SUBMITTED AT TIME OF ROOF PERMIT APPLICATION.
  
 10. ACCESSIBLE ROUTE REQUIRED, FBC A 202.3, 202.4.
 LANDINGS ARE SHOWN AT WHAT APPEARS TO BE THE MAIN
 ENTRANCES. ACCESSIBLE PARKING SHOULD BE ON AN
 ACCESSIBLE ROUTE, ACCESSIBLE ROUTE TO THE ALTERED AREA
 REQUIRED, REVISE TO COMPLY.
  
 11. FBC B 1026.6, 1022.4&5, ALSO SEE FIRE COMMENT
 REGARDING DOOR RATING. PLEASE ALSO SEE IBC 2012
 COMMENTARY PAGE 10-165; THIS INDICATES THAT NO OPENINGS
 ARE PERMITTED IN THE STAIR - THIS CAN BE SENT TO YOU
 UPON REQUEST BY EMAIL.
  