Text |
| 2017-09-22 17:45:12 | ****CORRECTIONS**** |
| | REVISED 9/27/17 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 3) SHEET A1.01 THE DEMO NOTE # 4 INDICATES THE REMOVAL |
| | OF THE FINISH FLOOR IN THE ATHLETIC ROOM. THE FINISH |
| | FLOOR SCHEDULE INDICATES THE FINISH FLOOR TO BE ECORE |
| | COMMERCIAL/ECO FIR RUBBER FLOORING/ GRANITE RUN 905. |
| | |
| | 804.3 TESTING AND IDENTIFICATION. INTERIOR FLOOR FINISH |
| | AND FLOOR COVERING MATERIALS SHALL BE TESTED BY AN |
| | AGENCY IN ACCORDANCE WITH NFPA 253 AND IDENTIFIED BY A |
| | HANG TAG OR OTHER SUITABLE METHOD SO AS TO IDENTIFY THE |
| | MANUFACTURER OR SUPPLIER AND STYLE, AND SHALL INDICATE |
| | THE INTERIOR FLOOR FINISH OR FLOOR COVERING |
| | CLASSIFICATION ACCORDING TO SECTION 804.2. |
| | |
| | 2ND REVIEW, A "CERTIFICATE OF COMPLIANCE" WAS PROVIDED, |
| | BUT THIS CITES ASTMD2859. FLOORING OTHER THAN THOSE OF |
| | A "TRADITIONAL NATURE" ARE TO BE TESTED TO NFPA 253. |
| | TESTING TO ASTM D 2859 IS ALSO REQUIRED. |
| | |
| | IT IS NOT CLEAR WHICH OF THE FLOORING IS PROPOSED; THE |
| | ONE LISTED ON THE PLAN IS NOT LISTED ON THE CERTIFICATE |
| | OF COMPLIANCE. |
| | |
| | PROVIDE COPIES OF THE TEST REPORTS (NFPA 253, ASTM D |
| | 2859). INDICATE WHICH FLOORING IS PROPOSED BY EITHER |
| | REVISING THE PLAN TO INCLUDE THE NAME CONSISTENT WITH |
| | THE TEST REPORTS, OR PROVIDE SPEC SHEETS AND MARK THE |
| | FLOORING PROPOSED. PER FBC B 804.3, THE MANUFACTURER |
| | AND STYLE SHOULD BE CONSISTENT WITH THE TEST REPORTS. |
| | |