| Plan Review Notes For Permit 17080851 |
| Permit Number |
17080851 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-18 18:05:07 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 480 VOLT SERVICE NEEDS TO BE SIGNED AND SEALED BY AN | | | ENGINEER, | | | | | | NEED FAULT CURRENT CALCULATION FOR THE SERVICE. |
|