2017-09-19 18:57:38PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR IS LOCATED IN EXPOSURE D WITH A 170
 MPH VULT WIND SPEED. BASED ON FBC-R 301.2.1, THE
 REQUIRED PRESSURE IS 49.9 PSF. THE ENGINEERING THAT WAS
 SUBMITTED HAS AN ALLOWABLE PRESSURE OF 40.38 PSF.
 SUBMIT ENGINEERING THAT HAS AN ALLOWABLE PRESSURE OF
 49.9 PSF OR HIGHER.