| Notes |
| Date |
Text |
| 2017-09-19 18:57:38 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR IS LOCATED IN EXPOSURE D WITH A 170 | | | MPH VULT WIND SPEED. BASED ON FBC-R 301.2.1, THE | | | REQUIRED PRESSURE IS 49.9 PSF. THE ENGINEERING THAT WAS | | | SUBMITTED HAS AN ALLOWABLE PRESSURE OF 40.38 PSF. | | | SUBMIT ENGINEERING THAT HAS AN ALLOWABLE PRESSURE OF | | | 49.9 PSF OR HIGHER. |
|