| Plan Review Notes For Permit 17080801 |
| Permit Number |
17080801 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-22 17:11:29 | SUBMITTAL DENIED | | | | | | 1) SUBMIT TWO SETS OF THE TEST REPORTS FOR THE SOUND | | | INSULATION UNDERLAYMENT BASED ON THE EXISTING SITE | | | CONDITIONS. DESCRIPTION OF EXISTING SITE CONDITIONS: | | | (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW | | | (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ). | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 WALLS, | | | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR | | | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E | | | 90. | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | |
|