| Notes |
| Date |
Text |
| 2017-08-29 11:19:38 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | | FS471. ALL OF THE DOCUMENTS SUBMITTED ARE PHOTOCOPIES. | | | | | | 2. REVIEW OF THE DELEGATED ENGINEERING (EARTHTECH) BY | | | THE STRUCTURAL ENGINEER OF RECORD IS REQUIRED, | | | FAC61G15-30, FBC 107. | | | | | | 3. FBC 107, PROVIDE FULL SIZE DOCUMENTS. IT APPEARS | | | THAT THE PLANS PREPARED BY EARTHTECH WERE REDUCED AS | | | WELL AS ONE OF THE SITE PLANS. SOME TEXT IS ILLEGIBLE. | | | | | | 4. WHO WILL MONITOR THE VIBROFLOTATION? PROVIDE | | | INFORMATION IN A LETTER. | | | | | | 5. IT IS SUGGESTED THAT YOU COORDINATE RESUBMITTAL WITH | | | EITHER ME OR STEVE KENNEDY. THIS IS NOT MANDATORY. | | | | | | 6. PRIOR TO COMMENCEMENT, CONTACT KEN CONRAD, | | | 561-805-6666 REGARDING A PRE CONSTRUCTION MEETING. | | | SUBJECT TO HIS DISCRETION, THIS MAY BE REQUIRED PRIOR | | | TO COMMENCEMENT. THIS TYPICALLY INCLUDES THE | | | CONTRACTOR, SI AND JOBSITE INSPECTOR. | | | | | | 7. FBC 107, PROVIDE AN EMAIL ADDRESS FOR THE CONTRACTOR | | | AS THIS IS THE PRIMARY MEANS OF COMMUNICATION FOR | | | PERMIT NOTIFICATION. | | | | | | |
|