Plan Review Notes
Plan Review Notes For Permit 17080795
Permit Number 17080795
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-29 11:19:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471. ALL OF THE DOCUMENTS SUBMITTED ARE PHOTOCOPIES.
  
 2. REVIEW OF THE DELEGATED ENGINEERING (EARTHTECH) BY
 THE STRUCTURAL ENGINEER OF RECORD IS REQUIRED,
 FAC61G15-30, FBC 107.
  
 3. FBC 107, PROVIDE FULL SIZE DOCUMENTS. IT APPEARS
 THAT THE PLANS PREPARED BY EARTHTECH WERE REDUCED AS
 WELL AS ONE OF THE SITE PLANS. SOME TEXT IS ILLEGIBLE.
  
 4. WHO WILL MONITOR THE VIBROFLOTATION? PROVIDE
 INFORMATION IN A LETTER.
  
 5. IT IS SUGGESTED THAT YOU COORDINATE RESUBMITTAL WITH
 EITHER ME OR STEVE KENNEDY. THIS IS NOT MANDATORY.
  
 6. PRIOR TO COMMENCEMENT, CONTACT KEN CONRAD,
 561-805-6666 REGARDING A PRE CONSTRUCTION MEETING.
 SUBJECT TO HIS DISCRETION, THIS MAY BE REQUIRED PRIOR
 TO COMMENCEMENT. THIS TYPICALLY INCLUDES THE
 CONTRACTOR, SI AND JOBSITE INSPECTOR.
  
 7. FBC 107, PROVIDE AN EMAIL ADDRESS FOR THE CONTRACTOR
 AS THIS IS THE PRIMARY MEANS OF COMMUNICATION FOR
 PERMIT NOTIFICATION.
  
  