| 2017-11-09 16:43:52 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17080793 |
| | 11/9/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) RESIDENTIAL MANUAL J CALCULATIONS CANNOT BE |
| | SUBMITTED FOR COMMERCIAL AC SYSTEMS. PLEASE REFER TO |
| | SECTION C403.2.1 CALCULATION OF HEATING AND COOLING |
| | LOADS: |
| | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE |
| | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR |
| | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE |
| | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT |
| | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE |
| | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE |
| | SIZING CALCULATION SHALL BE SUBMITTED WITH THE |
| | APPLICATION FOR THE MECHANICAL PERMIT. |
| | |
| | 2) PLEASE NOTE THAT THE MANUAL J CALCULATION |
| | INCORRECTLY INDICATES THE "FRONT DOOR FACING NORTH" |
| | HOWEVER THE FRONT DOOR IS FACING SOUTH. |
| | |
| | 3) THE COMCHECK COMPLIANCE CERTIFICATE INDICATES 16 |
| | SEER SYSTEMS, HOWEVER 14 SEER SYSTEMS ARE SHOWN IN THE |
| | AC SCHEDULE- PLEASE CORRECT. |
| | |
| | 4) THE REQUESTED MIAMI-DADE NOA FOR THE ROOF STAND WAS |
| | NOT SUBMITTED. PLEASE NOTE THAT THE PREVIOUSLY |
| | SUBMITTED NOA DID NOT HAVE THE RIGHT INSTALLATION |
| | DRAWINGS ATTACHED WITH THE COVER SHEETS. |
| | |