| 2017-10-23 17:30:46 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17080793 |
| | 10/23/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE RESUBMITTED PLAN APPEARS TO SHOW NEW ROUND |
| | OUTSIDE AIR DUCTS GOING THROUGH THE ROOF HOWEVER THEY |
| | ARE LABELED AS R/A (RETURN AIR) DUCTS AND THE SIZES OF |
| | THESE DUCTS ARE NOT INDICATED- PLEASE CORRECT. |
| | |
| | 2) THE RESUBMITTED PLAN IS NOW INDICATING 765 CFMS OF |
| | O/A FOR THE 5-TON SYSTEM WHICH IS 38% OF THE TOTAL 2000 |
| | CFM SUPPLY CFMS. BY INDUSTRY STANDARDS THIS WOULD BE |
| | CONSIDERED A LARGE AMOUNT OF O/A TO BE CONSTANTLY |
| | COOLED BY A 5-TON SYSTEM. PLEASE NOTE THAT A TEST AND |
| | BALANCE REPORT MUST BE SUBMITTED TO VERIFY THE O/A |
| | AMOUNT AND THE AIR DISTRIBUTION AS DESIGNED- SEE NOTE |
| | #13 ON SHEET M-1. |
| | |
| | 3) SHEETS M-1 & M-2: THE ARCHITECT IS INDICATING THAT |
| | THE ROOF TOP CONDENSER "SHALL BE INSTALLED TO RESIST |
| | WIND PRESSURES AT VELOCITIES INDICATED ON FBCM 301.15". |
| | PLEASE NOTE THAT THE MECHANICAL CODE SECTION 301.15 |
| | REFERENCES THE FLORIDA BUILDING CODE FOR WIND DESIGN, |
| | AND DOES NOT PROVIDE ANY DESIGN PRESSURES- PLEASE |
| | CORRECT AND PROVIDE ACCURATE WIND LOAD DESIGN CRITERIA |
| | . AS PREVIOUSLY REQUESTED, SUBMIT THE MIAMI-DADE NOA, |
| | OR THE FLORIDA PRODUCT APPROVAL FOR THE AC STAND WITH |
| | APPROVAL STAMP BY THE ARCHITECT OF RECORD. |
| | |