| 2017-10-20 15:06:35 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17080793 |
| | ADD: 329 CLEMATIS ST. SUITE: B |
| | CONT: DURHAM BROTHERS |
| | TEL: 561-662-0736 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. OCT. 20/ 2017 |
| | ACTION: BUILDING PROVIO |
| | |
| | 1) PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 2) PROVISO/ DEFERRED SUBMITTAL: IDENTIFY GLAZING/ |
| | MULLIONS. PLEASE IDENTIFY ON THE PRODUCT APPROVAL |
| | BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE |
| | SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS |
| | WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & |
| | HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF |
| | REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH |
| | OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. |
| | WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | 3) PROVISO/ DEFERRED SUBMITTAL: FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |