| Date |
Text |
| 2017-10-03 14:22:13 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED |
| | |
| | 6. EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES |
| | SHALL OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS |
| | TO PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN |
| | AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND |
| | NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR |
| | SURFACE. THE WALLS OR PARTITIONS SHALL EXTEND FROM THE |
| | WALL SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN |
| | 18 INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND |
| | THE OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE |
| | FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. PER |
| | FBC PL 405.3.5 URINAL STILL SHOWN ON ADA DETAIL AND |
| | NOTES. SHT.A-1 + P-2 PLEASE REMOVE |
| | |
| | 7. SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE LAVATORY'S. |
| | PER FBC ACC 606.2 |
| | |
| | 15. THE AAV VALVES THAT ARE SHOWN ON RISER APPEAR TO BE |
| | IN THE MIDDLE OF THE FLOORS PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 AAV STILL SHOWN IN MIDDLE OF FLOOR |
| | ON BRANCH DRAIN FOR SERVICE SINK NOT A REQUIRED VENT |
| | |
| | 16. THE BRANCH DRAIN FOR FUTURE IS SHOWN IN DIFFERENT |
| | LOCATION ON THE RISER AND FLOOR PLAN PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 17. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR |
| | TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 21. THE BACKFLOW ASSEMBLY SHALL BE LOCATED AT CITY |
| | WATER METER. PER WPB UTILITIES PLEASE SHOW BACKFLOW |
| | NEXT TO METER ON RISER AND FLOOR PLAN. |
| | |
| | NEW COMMENTS: |
| | |
| | 1. PLEASE LABEL FLORIDA ACCESSIBILITY CODE NOTES ON |
| | SHT. P-1. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHUT OFF VALVES ARE REQUIRED ON EACH DROP ON WATER |
| | PIPING. PER FBC PL 606.1 LOCATION OF FULL-OPEN VALVES. |
| | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE |
| | IN OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY |
| | RESIDENTIAL OCCUPANCIES. |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |