| 2017-09-28 14:12:25 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING, ENERGY |
| | CONSERVATION CODES |
| | PERMIT #17080793 |
| | 9/28/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE RESCHECK COMPLIANCE SUBMITTAL IS INDICATING THE |
| | PROJECT TYPE TO BE A "MULTI-FAMILY", HOWEVER THE |
| | PROPOSED PROJECT IS CHANGE OF OCCUPANCY FROM MERCANTILE |
| | TO ASSEMBLY AND MUST BE IN COMPLIANCE WITH THE |
| | COMMERCIAL CODES. PLEASE SEE SECTION C101.5.1 FBC-14 |
| | ENERGY CONSERVATION AND PROVIDE EITHER A FLORIDA |
| | ENERGYGAUGE COMPLIANCE SUBMITTAL OR A COMCHECK |
| | COMPLIANCE CERTIFICATE. |
| | |
| | 2) M-2: THE 5-TON AC SYSTEM WHICH IS PRESUMED TO |
| | PRODUCE APPROXIMATE 2000 CFMS WOULD BE UNDERSIZED TO |
| | CONDITION 1040 CFMS OF OUTSIDE AIR ACCORDING TO |
| | ASHRAE/ACCA STANDARDS. THE TYPICAL PERCENTAGE OF |
| | OUTSIDE AIR TO SUPPLY AIR WOULD RANGE AROUND 17-20%. IN |
| | ADDITION THE 14X12 DUCT THAT IS BOTH SUPPLYING THE O/A |
| | AND RETURNING 1370 CFMS OF AIR FROM THE SPACE IS |
| | UNDERSIZED FOR THE TOTAL 2410 CFMS OF AIR- PLEASE |
| | CORRECT. |
| | |
| | 3) M-2, AC EQUIPMENT SCHEDULE: PROVIDE THE KW |
| | CAPACITIES OF THE AIR HANDLER HEAT STRIPS AND THE TOTAL |
| | SUPPLY CFMS OF EACH SYSTEM. |
| | |
| | 4) M-2: THE OUTSIDE AIR INLETS APPEAR TO BE WITHIN THE |
| | REQUIRED 10' CLEARANCE SPACE TO THE ADJACENT OPEN |
| | PARKING AREA- SEE SECTION 401.4 AND CORRECT. |
| | |
| | 5) M-1: THE REQUESTED WIND LOAD ENGINEERING AND NOA FOR |
| | THE AC STANDS WAS NOT PROVIDED. PROVIDE ON THE PLAN THE |
| | WIND DESIGN CRITERIA USED TO DETERMNINE THE DESIGN |
| | PRESSURES AND TIE DOWN REQUIREMENTS- SEESECTION 301.15 |
| | FBC-14 MECH. & 1609 FBC-14 BUILDING. |
| | |
| | 6) PROVIDE THE MIAMI-DADE NOAS OR FLORIDA PRODUCT |
| | APPROVALS FOR THE ROOF STANDS AND LOUVERS- RULE 9N-3 |
| | FAC. |
| | |