| 2017-09-27 08:03:13 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17080793 |
| | ADD: 329 CLEMATIS ST. SUITE: B |
| | CONT: DURHAM BROTHERS |
| | TEL: 561-662-0736 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. SEPT. 27/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. SITE THE OLD MYERS LUGGAGE STORE. A CHANGE |
| | OF OCCUPANCY TO A A2 |
| | |
| | 1A)SEMI-COMPLIED. SHEET A-1 THE EAST 6 INCH FRAME WALL |
| | WILL NEED TO PROVIDE EITHER A U. L. LISTING, OR GYPSUM |
| | ASSOCIATION LISTING, WITH TYPE OF FRAMING MEMBER, |
| | SPACING OF FRAMING MEMBER, TYPE OF DRYWALL, THICKNESS |
| | AND LAYERS TO COMPLETE THE WALL ASSEMBLY FOR A 2 HOUR |
| | FIRE RATING. . FBC-B 707.3.9 SEPARATED OCCUPANCIES & |
| | 707.5 CONTINUITY.1ST ROUND OF COMMENTS. THE COVERSHEET |
| | DOES NOT PROVIDE THE REQUIRED OCCUPANCY SEPARATION |
| | REQUIREMENT FOUND IN TABLE 508.4 OF THE 2014 FBC-B. |
| | SHEET A-1 DOES INDICATE EXISTING 2 HR. OCCUPANCY |
| | SEPARATION BUT DOES NOT DECLARE THE TYPE OF WALL |
| | ASSEMBLY TO MAKE UP THE EXISTING 2 HR. FIRE BARRIER. |
| | FBC-B 707.3.9 SEPARATED OCCUPANCIES & 707.5 CONTINUITY. |
| | |
| | 1B) COMPLETED. |
| | |
| | 1C) 2ND REQUEST. SHEET A-1 RESTATES THE CODE SECTION |
| | MANY TIMES, DOES NOT SHOW CODE COMPLIANCE. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH |
| | DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, |
| | IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 1ST ROUND COMMENT. PLEASE PROVIDE COMPLIANCE WITH THE |
| | 2014 FBC-EXISTING BUILDING CODE SECTION 1012.1.2 FIRE |
| | PROTECTION AND INTERIOR FINISH. THE PROVISIONS OF |
| | SECTIONS 1012.2 AND 1012.3 FOR FIRE PROTECTION AND |
| | INTERIOR FINISH, RESPECTIVELY, SHALL APPLY TO ALL |
| | BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 1D) 2ND REQUEST. PLEASE NOTE THE SEATING AGAINST THE |
| | EAST WALL HAS BEEN ELIMINATED, NOT SHOWING ANY DENSITY |
| | WILL TAKE THE MOST RESTRICTIVE AT 5 SQ. FT./ OCCUPANT. |
| | PLEASE REVIEW UNDER CHAPTER 10 OF THE EXISTING BUILDING |
| | CODE THE REQUIREMENT FOR FIRE SPRINKLERS. 2014 EXT. |
| | BLDG. CODE 1012.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 1012.2.1 AND 1012.2.2. |
| | EXST. BLDG. CODE 1012.2.1 FIRE SPRINKLER SYSTEM. WHERE |
| | A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. |
| | 2014 FBC-B SECTION F] 903.2.1.2 GROUP A-2. AN AUTOMATIC |
| | SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2 |
| | OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS |
| | EXISTS: 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR |
| | MORE. |
| | |
| | 2) SHEET A-1: |
| | 2A-B) COMPLIED. |
| | |
| | 2C) 2ND REQUEST. SHEET A1 SHOWS 4 ACCESSIBLE SEATS. THE |
| | LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE : |
| | 2014 FBC-ACCESSIBILITY CODE; 226.1 WHERE DINING |
| | SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR |
| | DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND |
| | STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| | WITH 902. 80 SEATS X 0.05= 4.0 OR 4 SEATS,3 SHOWN ON |
| | PLANS. |
| | |
| | 2D) 2ND REQUEST, NO DROPPED PORTION OF BAR FOR |
| | HANDICAPPED SEATING AT BAR. FBC-ACCESSIBILITY CODE |
| | 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. THE PLANS DO NOT SHOW |
| | COMPLIANCE WITH: 902.1 .DINING SURFACES AND WORK |
| | SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY |
| | 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT |
| | LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. |
| | |
| | 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND |
| | 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 2E) COMPLIED. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) 2ND REQUEST. NOTE THE ARCHITECT OF RECORD IS SIGNING |
| | AND SEALING COMPUTER SOFTWARE PROGRAM. PLEASE BE AWARE |
| | WITHIN THE SOFTWARE GROGRAM YOU HAVE TAKEN CREDIT FOR 3 |
| | FOOT PARAPETS ON ALL SIDES OF THE ROOF. ON THE NORTH |
| | AND EAST SIDES OF THE BUILDING THERE IS NO 3 FOOT |
| | PARAPET, PLEASE CORRECT THE INPUT DATA TO PROVIDE |
| | PRESSURES FOR ROOF ZONE 3. GOOGLE EARTH AND A |
| | COUNTYWIDE GIS PROGRAM ALLOWS FOR AERIAL VIEWS OF |
| | BUILDINGS. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF |
| | MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE |
| | 1609.7.2. HEIGHT AND EXPOSURE. |
| | |
| | THE MECA SOFTWARE PROGRAM SUBMITTED IS VERY LIGHT, HARD |
| | TO READ AND WILL NOT MEET THE QUALITY OF PLANS |
| | REQUIRED, FOR SCANNING INTO RECORD RETENTION. 107.2.1.4 |
| | QUALITY OF BUILDING PLANS. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | |
| | THE 3RD ISSUE WITH THE ARCHITECT SIGNING AND SEALING |
| | THE WIND DESIGN REPORT IS ONLY THE FRONT PAGE OF THE |
| | REPORT IS SEALED, NOT ALL PAGES. FL ADMIN CODE |
| | 61G16.003(1) ARCHITECTS.PLANS, SPECIFICATIONS, REPORTS |
| | OR OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL |
| | AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE |
| | SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET A-3. PLEASE PROVIDE |
| | COMPLIANCE WITH FBC-B WIND DESIGN. THE PLANS REFERENCE |
| | THE RESIDENTIAL CODE, R703.13, R616.4, TABLE R301.2(2) |
| | & R301.2(2). |
| | |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| | INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| | REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | 2. RISK CATEGORY. |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 5-6) COMPLIED. |
| | |
| | 7) PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 8) PROVISO/ DEFERRED SUBMITTAL: IDENTIFY GLAZING/ |
| | MULLIONS. PLEASE IDENTIFY ON THE PRODUCT APPROVAL |
| | BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE |
| | SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS |
| | WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & |
| | HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF |
| | REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH |
| | OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. |
| | WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | 9) PROVISO/ DEFERRED SUBMITTAL: FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 10) COMPLIED. THRESHOLDS ACCESS. CODE 404.2.5 |
| | |
| | 11) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |