| 2017-08-30 10:23:26 | 1ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING, |
| | ENERGY CONSERVATION. |
| | PERMIT #17080793 |
| | 8/30/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION |
| | AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT FOR |
| | THE CHANGE OF OCCUPANCY FROM M TO A-2. SEE SECTION |
| | C401.2 FOR COMPLIANCE PATH INFORMATION. |
| | |
| | 2) SUBMIT COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC-14 |
| | ENERGY CONSERVATION. |
| | C403.2.1 CALCULATION OF HEATING AND COOLING LOADS. |
| | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE |
| | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR |
| | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE |
| | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT |
| | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE |
| | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE |
| | SIZING CALCULATION SHALL BE SUBMITTED WITH THE |
| | APPLICATION FOR THE MECHANICAL PERMIT. |
| | PLEASE NOTE THE ILLEGIBLE CALCULATION COPIED AND PASTED |
| | ON SHEET M-2 APPEARS TO HAVE BEEN PERFORMED USING |
| | MANUAL J FOR RESIDENTIAL SYSTEMS- NOT ACCEPTABLE- SEE |
| | ABOVE. |
| | |
| | 3) THE M-1 PLAN AND THE EQUIPMENT SCHEDULE ARE |
| | INDICATING THE NEW AC SYSTEMS TO BE SPLIT-SYSTEMS, |
| | HOWEVER THEY ARE LABELED AS RTU'S ON THE LAYOUT PLAN- |
| | PLEASE CORRECT. |
| | |
| | 4) M-2: PLEASE INDICATE THE SUPPLY AND RETURN CFMS AT |
| | EACH DIFFUSER AND GRILL SHOWN ON THE LAYOUT PLAN. |
| | |
| | 5) M-2: SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR |
| | SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1. |
| | PLEASE SHOW THE LOCATIONS ON THE PLAN. PLEASE NOTE THAT |
| | AN EXEMPTION CAN BE APPLIED IF THE MANUFACTURER'S |
| | SPECIFICATIONS INDICATE SYSTEMS ARE NOT CAPABLE OF |
| | PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | 6) M-2: INDICATE HOW OUTDOOR AIR IS BEING PROVIDED TO |
| | THE NEW AIR HANDLERS, AND COMPLY WITH SECTION |
| | C403.2.4.4. FOR REQUIRED DAMPER. |
| | |
| | 7) M-2: PROVIDE DUCT HANGING AND CONNECTION DETAILS PER |
| | SMACNA STANDARDS. |
| | |
| | 8) M-2: PROVIDE CONDENSATE DISPOSAL PLANS AND DETAILS |
| | PER SECTION 307. |
| | |
| | 9) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS |
| | OF THE CONDENSERS AND THEIR DISTANCES FROM THE ROOF |
| | EDGES. PLEASE PROVIDE ADDITIONAL CLEARANCE DISTANCE |
| | MEASUREMENTS FOR O/A INTAKES TO EXHAUST AND VENT |
| | OPENINGS- SEE SECTIONS 304.11 AND 401.4. |
| | |
| | 10) PROVIDE A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA |
| | FOR THE CONDENSER STAND WITH REVIEW STAMP BY THE |
| | ENGINEER OF RECORD. THE EOR SHALL CIRCLE, HIGHLIGHT, OR |
| | OTHERWISE MARK ALL APPLICABLE INSTALLATION DETAILS AND |
| | DESIGN PRESSURES SHOWN IN THE DOCUMENT, AND ALSO |
| | PROVIDE THE WIND DESIGN CRITERIA ON THE PLAN- SECTION |
| | 301.15. |
| | |