Text |
| 2017-08-23 14:08:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEET E-1 HAS SEVERAL NOTES (THE NOTES THAT ARE NOT |
| | NUMBERED) THAT APPLY TO RESIDENTIAL INSTALLATIONS. |
| | EXAMPLE: 75% OF LAMPS SHALL BE HIGH EFFICIENCY, |
| | RECEPTACLES TO BE TAMPER RESISTANT, AFCI PROTECTION, |
| | ETC. REMOVE ALL NOTES NOT APPLICABLE TO PROJECT. FBC |
| | 107.2.1 |
| | 2. PROVIDE SHOW WINDOW OUTLET PER CODE. NEC 210.62 |
| | 3. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW |
| | LIGHTING. FBC CE 405.2.4 |
| | 4. PROVIDE LIGHT FIXTURE SCHEDULE. FBC 107.2.1 |
| | 5. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING |
| | COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5 |
| | 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. NO AUTOMATIC CONTROL IS |
| | CURRENTLY SHOWN. FBC CE 405.2.2, 405.2.2.2 |
| | 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR SYSTEMS TO INCLUDE BUT NOT BE LIMITED TO |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | WALK IN COOLER, ETC. FBC 105.1 |
| | 8. CIRCUIT 16,18 IS DESIGNATED IN PANEL SCHEDULE FOR |
| | WALK IN COOLER, BUT CIRCUIT 18 IS SHOWN FEEDING SEVERAL |
| | RECEPTACLES. CORRECT DISCREPANCY. FBC 107.2.1, NEC |
| | 215.5, 408.4 |
| | 9. PROVIDE REQUIRED GFCI SERVICE OUTLET FOR A/C |
| | EQUIPMENT. NEC 210.63 |
| | 10. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED |
| | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | 11. PANEL SCHEDULE SHOWS AHU-1, AHU-2, CU-1, AND CU-2. |
| | ELECTRICAL PLAN SHOWS RTU-1 ONLY. PROVIDE CORRECTION, |
| | UPDATE PANEL LOAD IF NECESSARY. FBC 107.2.1; NEC 220, |
| | 408.4 |
| | 12. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 13. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9 |
| | 14. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24. |
| | 15. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | USING METHOD FOR COMMERCIAL SERVICE. CURRENT LOAD |
| | STATED FOR RECEPTACLES IS NOT ACCURATE. NEC 220; FBC |
| | 107.2.1 |
| | 16. NOTE UNDER PANEL SCHEDULE STATES THAT ALL 15 AN 20 |
| | AMP BREAKERS SHOULD BE AFCI TYPE. CLARIFY AND/OR |
| | CORRECT. FBC 107.2.1; NEC 210.12 |
| | 17. NOTE ON SHEET E-2 STATES THAT "SMOKE DETECTORS TO |
| | BE HARD WIRED WITH BATTERY BACK UP". NO SMOKE DETECTORS |
| | SHOWN ON PLAN. A SEPARATE PERMIT IS REQUIRED FOR FIRE |
| | ALARM INSTALLATIONS. PLEASE CLARIFY AND/OR CORRECT. FBC |
| | 105.1, 107.2.1 |
| | 18. SCOPE OF WORK ON C-1 STATES THAT THERE WILL BE 4 |
| | NEW SERVICES WITH 4 NEW PANELS. THIS WORK IS NOT |
| | REFLECTED ON PLAN. PLEASE CLARIFY AND/OR CORRECT. FBC |
| | 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |