| 2018-01-22 08:29:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PER SECTION C101.4.4 OF THE FBC ENERGY CONSERVATION, |
| | WHEN A CHANGE OF OCCUPANCY OCCURS, THE INSTALLED |
| | LIGHTING MUST COMPLY WITH FBC ENERGY CONSERVATION, |
| | SECTION C405.5. PROVIDE CHART OF INTERIOR LIGHTING |
| | POWER ALLOWANCES EXPRESSED IN WATTAGE PER THE FBC |
| | ENERGY COSERVATION IN RELATION TO THE WATTAGE OF THE |
| | CONNECTED INTERIOR LIGHTING TO COMPLY WITH CODE. FBC EC |
| | 405.5.2 |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| | 3. PLAN STATES THERE ARE NO CHANGES TO THE ELECTRICAL |
| | SYSTEM, BUT NEW ELECTRICAL WORK IS SHOWN. REMOVE |
| | CONFLICTING STATEMENT. FBC 107.2.1 |
| | 4. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. NEC |
| | 422.52 |
| | 5. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. FBC EC 405.2.2, |
| | 405.2.2.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |