| Date |
Text |
| 2017-09-06 12:54:55 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17080780 |
| | ADD: 4317 NORTHSHORE DR. |
| | CONT: BUILT SOLID CONSTRUCTION |
| | TEL: 561-333-2593 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. SEPT. 06/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE ADDITIONAL SQUARE FOOTAGE OF AN |
| | ADJACENT TENANT SPACE WILL BE CONSIDERED A CHANGE IN |
| | OCCUPANCY, PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. |
| | 2014 FBC-EXIST. BUILD. CODE. 1001.3.1 PARTIAL CHANGE OF |
| | OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN |
| | EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY |
| | CLASSIFICATION, SECTION 1012 SHALL APPLY. PLEASE UPDATE |
| | PLANS AS SUCH. |
| | |
| | 2) PLEASE NOTE WITH THIS BEING A CHANGE OF OCCUPANCY |
| | THE DESIGNER OF RECORD MUST MEET THE REQUIREMENTS OF |
| | 1012.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH |
| | SEPARATION. THE ORIGINAL PERMIT # 13050463 COMMENT (1A) |
| | REQUIRED OCCUPANCY SEPARATION WITH A 2 HR. FIRE RATED |
| | FIRE BARRIER( FBC-B TABLE 503 DAYCARE- BUSINESS) ON |
| | EACH SIDE OF THE TENANT SPACE. THE SUBMITTED SET OF |
| | PLANS STILL SHOWS A ONE HOUR FIRE SEPARATION WALL. |
| | PROVIDE THE WALL ASSEMBLY, COMPOSITION OF THIS WALL. |
| | |
| | 3) IN THE NEW AREA WHERE THE TENANT SEPARATION OCCURS |
| | THE PLANS INDICATE AN ASSEMBLY OCCUPANCY AND BLOCK WALL |
| | CONSTRUCTION. PLEASE PROVIDE THE ASSEMBLY FOR THIS WALL |
| | FOR A REQUIRED 2 HR. FIRE BARRIER FOR ASSEMBLY TO A I-4 |
| | OCCUPANCY. UNDER THE 2014 FBC-B THERE IS NO DAYCARE |
| | OCCUPANCY, YOU WILL SEE UNDER AN I-4 OCCUPANCY DAYCARES |
| | ARE LISTED. |
| | |
| | 4) PLEASE PROVIDE THE TOTAL AMOUNT OF CHILDREN AND AGES |
| | OF THE CHILDREN. PLEASE BE SPECIFIC AS HOW MANY |
| | CHILDREN THERE WILL BE ATTENDING BETWEEN THE AGES OF |
| | 0-2 YEARS OLD AND 2-11. |
| | 2014 FBC-B 308.6.1. CHILDREN BETWEEN THE AGES OF 0-2 |
| | YEARS OLD ARE CONSIDERED EDUCATIONAL AND THE OCCUPANT |
| | LOAD IS TAKEN AT 20 SQ. FT./ CHILD. THE DAYCARE (I-4) |
| | OCCUPANCY IS TAKEN AT 35 SQ. FT. / CHILD. SEE TABLE |
| | 1004.1.2. |
| | |
| | 5) THE DESIGNER OF RECORD ALSO NEEDS TO PROVIDE |
| | OCCUPANCY SEPARATION BETWEEN THE 0-2 YEAR OLDS |
| | (EDUCATIONAL) AND THE I-4 (DAYCARE) 2-11 YEAR OLDS AS |
| | PER TABLE 1004.1.2 AND OPENING PROTECTIVES IN |
| | COMPLIANCE WITH FBC-B TABLE 716.5. |
| | |
| | 6) SHEET 1. PLEASE SHOW COMPLIANCE WITH FBC-B 466.3 |
| | BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL BE |
| | DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM THE |
| | OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL BE |
| | READILY ACCESSIBLE TO THE STAFF. |
| | |
| | 7) SHEET 1. THIS FACILITY IS NO LONGER ONE SINGLE ROOM. |
| | PLEASE SHOW COMPLIANCE WITH FBC-B 466.7 DETECTION AND |
| | ALARM SYSTEMS. DAY CARE OCCUPANCIES SHALL BE PROVIDED |
| | WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION 907 |
| | AND THIS SECTION. |
| | |
| | 8) SHEET 1. PLEASE SHOW COMPLIANCE WITH FBC-B: |
| | 2014 FBC-B 466.10.5 SMOKE DETECTION SYSTEMS. |
| | 466.10.5.3 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED |
| | BY THE BUILDING ELECTRICAL SYSTEM. |
| | 466.10.5.4 SINGLE-STATION SMOKE ALARMS SHALL BE |
| | PROVIDED IN ALL ROOMS USED FOR SLEEPING. |
| | |
| | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |