2017-08-18 12:25:10RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- FLORIDA PRODUCT APPROVAL FL2533-R16 SUBMITTED WAS
 REVISED. PROVIDE CURRENT REVISED FLORIDA PRODUCT
 APPROVAL FL2533-R18.
 FAC 61G20-3.001.
  
 2- SELECTED APPROVED ASSEMBLY W-44 DOESN'T MEET THE
 DESIGN PRESSURES FOR ROOF ZONE #3. THIS PROPERTY IS
 LOCATED IN EXPOSURE "D". THE DESIGN PRESSURES FOR THE
 CORNER AREAS ARE HIGHER THAN -105PSF. NEED TO SELECT
 ASSEMBLY THAT MEETS THE DESIGN PRESSURES FOR ALL ROOF
 ZONES, INCLUDING ROOF ZONE #3 AS REQUIRED TO MEET THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  