| Plan Review Notes For Permit 17080757 |
| Permit Number |
17080757 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-18 12:25:10 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- FLORIDA PRODUCT APPROVAL FL2533-R16 SUBMITTED WAS | | | REVISED. PROVIDE CURRENT REVISED FLORIDA PRODUCT | | | APPROVAL FL2533-R18. | | | FAC 61G20-3.001. | | | | | | 2- SELECTED APPROVED ASSEMBLY W-44 DOESN'T MEET THE | | | DESIGN PRESSURES FOR ROOF ZONE #3. THIS PROPERTY IS | | | LOCATED IN EXPOSURE "D". THE DESIGN PRESSURES FOR THE | | | CORNER AREAS ARE HIGHER THAN -105PSF. NEED TO SELECT | | | ASSEMBLY THAT MEETS THE DESIGN PRESSURES FOR ALL ROOF | | | ZONES, INCLUDING ROOF ZONE #3 AS REQUIRED TO MEET THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH | | | EDITION (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|