Plan Review Notes
Plan Review Notes For Permit 17080749
Permit Number 17080749
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-23 07:23:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS. THE SIGNATURE ON THE DRAWINGS IS NOT AN
 ORIGINAL HANDWRITTEN SIGNATURE.
  
 2) THE GENERAC MODELS G007043-0 OR G007042-0 THAT WERE
 INDICATED FROM THE MANUFACTURER'S SPECIFICATIONS ARE
 NOT LISTED FOR USE WITH THE GENERATOR PAD DOCUMENTS
 THAT WERE SUBMITTED. PLEASE SUBMIT THE CORRESPONDING
 DOCUMENTS. FBC 107.2.1