| Plan Review Notes For Permit 17080743 |
| Permit Number |
17080743 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2018-08-16 10:48:06 | PLAN | | | REVIEW COMMENTS | | | | | | 5TH REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | 1) SEE BUILDING REVIEW COMMENTS FOR ENERGY CODE | | | COMPLIANCE. | | | | | | 2) PROVIDE HEATING AND COOLING EQUIPMENT SIZING | | | CALCULATIONSFOR THE NEW ADDITION. FBCR-M1401.3 | | | | | | 3) CLARIFY THAT THE PROPOSED MINI-SPLIT SYSTEM WILL | | | PROVIDE THE REQUIRED HEATING FOR THE NEW ADDITION. FBC | | | 107.2.1 |
|