| 2018-08-16 10:10:59 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 17080743 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 5TH REVIEW: FBC FIFTH EDITION (2014) |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) COMPLIED. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) PARTICAL COMPLIANCE. EXPLAIN WHAT THE "INSIDE |
| | BITUMEN FOAM" MEANS ON SHEET A3.0. ON SHEET A3.0 THE |
| | ROOFING MATERIAL IS SPECIFIED AS ASPHALT TILE ROOF ON A |
| | 90# HOT MOPPED TO A 30# BASE SHEET. PLEASE CLARIFY. FBC |
| | 107.2.1 WILL ASPHALT SHINGLES OR CONCRETE ROOF TILE BE |
| | INSTALLED? HOT MOPPED 90# IS NOT USED AS AN |
| | UNDERLAYMENT FOR ASPHALT SHINGLES. |
| | PATIALLY ADDRESSED-WHAT IS THE BITUMEN FOAM FOR? IF |
| | ATTACHMENT THAN PRODUCT APPROVAL NEEDED. |
| | THE NAILS SHOULD BE AS FOLLOWS: |
| | FBC R803.2.3.1]SHEATHING FASTENING. |
| | SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113) |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) COMPLIED. |
| | |
| | NEW COMMENTS: |
| | |
| | 13) SEE #3 |
| | |
| | 14) COMPLIED. |
| | |
| | NEW COMMENTS 8/15/18: |
| | |
| | 15. [FBC EXISTING 807.2]WHAT ARE THE NEW TRUSSES |
| | BEARING ON? PROVIDE ENGINEERING THAT THE EXISTING WALLS |
| | CAN BEAR THE NEW TRUSSES AND ROOF. TRUSSES APPEAR TO BE |
| | HANGING FROM EXISTING AT LAUNDY ROOM WALL. IS THAT THE |
| | CASE AND HOW CAN EXISTING SUPPORT THE NEW LOADS? |
| | |
| | 16. [FBC EXISTING 807.2]WHERE REMOVING EXTERIOR WALL IT |
| | APPEARS THAT AN 8? X 8? BEAM IS LEFT BEHIND TO BEAR THE |
| | EXISTING AND THE NEW TRUSSES. PROVIDE ENGINEERING TO |
| | SHOW THAT BEAM WOULD BE SUFFICIENT TO SUPPORT ALL |
| | LOADS. |
| | I SEE THAT YOU END THE ADDITION EVEN WITH THE LAUNDRY. |
| | CONSIDER PUSHING THE ADDITION BACK A COUPLE OF FEET SO |
| | THAT THE EXISTING EXTERIOR WALL CAN REMAIN WITHOUT LOSS |
| | OF NEW BEDROOM SIZE. |
| | |
| | 17. [FBC R802.11]SHOW CONNECTOR FOR EACH TRUSS. |
| | |
| | 18. [FBC 2319.17.2.4.4]WHAT IS THE GABLE END MATERIAL. |
| | PROVIDE DETAIL OF GABLE END AND HOW ID TRANSITIONS TO |
| | THE BEAM. |
| | |
| | 19. PLEASE SHOW SKLIGHTS ON ROOFING PLAN FOR NUMBER OF |
| | SKYLIGHTS AND LOCATION. |
| | |
| | 20. [FBC ENERGY R401.2]THE PERMIT HA TWO ENERGY CALCS |
| | ATTACHED. ONE IS PERFORMANCE AND ONE IS ENVELOPE. BASED |
| | ON DATE IT LOOKS LIKE THE ENERGY CALCS BASED ON |
| | PERFORMANCE IS THE CURRENT. IF SO, THERE ARE SOME |
| | ERRORS ON THE REPORT. |
| | OWNER, DESIGN LOCATION, BUILDER NAME, CLIMATE, ROOF, |
| | ATTIC AND SKYLIGHTS NEED TO BE ADDED. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |