Plan Review Notes
Plan Review Notes For Permit 17080743
Permit Number 17080743
Review Stop B
Sequence Number 5
Notes
Date Text
2018-08-16 10:10:59****CORRECTIONS****
 W.P.B. PERMIT: 17080743
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 5TH REVIEW: FBC FIFTH EDITION (2014)
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) PARTICAL COMPLIANCE. EXPLAIN WHAT THE "INSIDE
 BITUMEN FOAM" MEANS ON SHEET A3.0. ON SHEET A3.0 THE
 ROOFING MATERIAL IS SPECIFIED AS ASPHALT TILE ROOF ON A
 90# HOT MOPPED TO A 30# BASE SHEET. PLEASE CLARIFY. FBC
 107.2.1 WILL ASPHALT SHINGLES OR CONCRETE ROOF TILE BE
 INSTALLED? HOT MOPPED 90# IS NOT USED AS AN
 UNDERLAYMENT FOR ASPHALT SHINGLES.
 PATIALLY ADDRESSED-WHAT IS THE BITUMEN FOAM FOR? IF
 ATTACHMENT THAN PRODUCT APPROVAL NEEDED.
 THE NAILS SHOULD BE AS FOLLOWS:
 FBC R803.2.3.1]SHEATHING FASTENING.
 SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113)
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 NEW COMMENTS:
  
 13) SEE #3
  
 14) COMPLIED.
  
 NEW COMMENTS 8/15/18:
  
 15. [FBC EXISTING 807.2]WHAT ARE THE NEW TRUSSES
 BEARING ON? PROVIDE ENGINEERING THAT THE EXISTING WALLS
 CAN BEAR THE NEW TRUSSES AND ROOF. TRUSSES APPEAR TO BE
 HANGING FROM EXISTING AT LAUNDY ROOM WALL. IS THAT THE
 CASE AND HOW CAN EXISTING SUPPORT THE NEW LOADS?
  
 16. [FBC EXISTING 807.2]WHERE REMOVING EXTERIOR WALL IT
 APPEARS THAT AN 8? X 8? BEAM IS LEFT BEHIND TO BEAR THE
 EXISTING AND THE NEW TRUSSES. PROVIDE ENGINEERING TO
 SHOW THAT BEAM WOULD BE SUFFICIENT TO SUPPORT ALL
 LOADS.
 I SEE THAT YOU END THE ADDITION EVEN WITH THE LAUNDRY.
 CONSIDER PUSHING THE ADDITION BACK A COUPLE OF FEET SO
 THAT THE EXISTING EXTERIOR WALL CAN REMAIN WITHOUT LOSS
 OF NEW BEDROOM SIZE.
  
 17. [FBC R802.11]SHOW CONNECTOR FOR EACH TRUSS.
  
 18. [FBC 2319.17.2.4.4]WHAT IS THE GABLE END MATERIAL.
 PROVIDE DETAIL OF GABLE END AND HOW ID TRANSITIONS TO
 THE BEAM.
  
 19. PLEASE SHOW SKLIGHTS ON ROOFING PLAN FOR NUMBER OF
 SKYLIGHTS AND LOCATION.
  
 20. [FBC ENERGY R401.2]THE PERMIT HA TWO ENERGY CALCS
 ATTACHED. ONE IS PERFORMANCE AND ONE IS ENVELOPE. BASED
 ON DATE IT LOOKS LIKE THE ENERGY CALCS BASED ON
 PERFORMANCE IS THE CURRENT. IF SO, THERE ARE SOME
 ERRORS ON THE REPORT.
 OWNER, DESIGN LOCATION, BUILDER NAME, CLIMATE, ROOF,
 ATTIC AND SKYLIGHTS NEED TO BE ADDED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  