2018-07-10 17:36:57PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
 2) COMPLIED.
 3) COMPLIED.
 4) THE ATTIC VENT RATIO IS LISTED AS 300 SQFT ON THE
 ENERGY FORMS. FBC-R 806.2 THE MINIMUM NET FREE
 VENTILATION AREA SHALL BE 1/150 OF THE VENTED SPACE.
 THE EXCEPTION THAT ALLOWS THE 1/300 NET VENTILATION
 REQUIRES THAT AT LEAST 40 PERCENT AND NOT MORE THAN 50
 PERCENT OF THE REQUIRED VENTILATING AREA IS PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC
 OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NO
 MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST
 POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF
 FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF
 UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914
 MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL
 BE PERMITTED. THE PLANS DO NOT SHOW
 5) COMPLIED.
  
 NEW COMMENTS:
 THE ENERGY FORMS CONTAIN NUMEROUS ERRORS. SEE NEW
 COMMENTS BELOW.
 1) THE DESIGN LOCATION ON THE ENERGY FORMS IS LISTED AS
 ST LUCIE, THIS PROJECT IS LOCATED IN WEST PALM BEACH,
 FL. WHICH IS IN PALM BEACH COUNTY. ON PAGE 2, THE TMY
 SITE IS INCORRECTLY LISTED AS VERO BEACH.
  
 2) THE ROOF IS LISTED AS BARREL TILE INSTEAD OF ASPHALT
 SHINGLES.
  
 3) ON PAGE 1, THERE IS A WOOD FRAME EXTERIOR WALL
 LISTED AND ALL OF THE EXTERIOR WALLS OF THE ADDITION
 ARE CBS.
  
 4) LIST THE OWNER'S AND BUILDER'S NAMES IN THE AREA AT
 THE TOP OF PAGE 1.
  
  
  
  
  
  