2018-07-11 11:44:16PLAN
 REVIEW COMMENTS
  
 4TH REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) PARTIAL COMPLIANCE. EXPLAIN WHAT THE "INSIDE BITUMEN
 FOAM" MEANS ON SHEET A3.0. ON SHEET A3.0 THE ROOFING
 MATERIAL IS SPECIFIED AS ASPHALT TILE ROOF ON A 90# HOT
 MOPPED TO A 30# BASE SHEET. PLEASE CLARIFY. FBC 107.2.1
 WILL ASPHALT SHINGLES OR CONCRETE ROOF TILE BE
 INSTALLED? HOT MOPPED 90# IS NOT USED AS AN
 UNDERLAYMENT FOR ASPHALT SHINGLES.
  
 4) COMPLIED.
  
 5) PARTIAL COMPLIANCE. STILL NEED THE PRODUCT APPROVALS
 FOR THE SKYLIGHT AND THE ROOF COVERING MATERIAL. FBC
 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001
 PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA
 NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM
 DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING
 MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL MULLIONS,
 SKYLIGHTS AND EXTERIOR DOOR TYPES.
  
 6) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 NEW COMMENTS:
  
 13) ON SHEET A3.0, THE REVISED NOTES SPECIFY 10D NAILS
 FOR THE ROOF SHEATHING AND THE PREVIOUS NOTE SPECIFIES
 8D RING SHANK NAILS. SPECIFY ONE OR THE OTHER. FBC
 107.2.1
  
 14) THE WINDOW AND DOOR SCHEDULE AND PRESSURES ON SHEET
 A4.0 HAVE NUMEROUS ERRORS. THIS PROJECT IS LOCATED IN
 EXPOSURE "C" WITH A 170MPH VULT WINDSPEED. THE ROUGH
 OPENING SIZES FOR THE WINDOWS AND SLIDING GLASS DOOR
 ARE INCORRECT. THE ROUGH OPENINGS SHOULD BE LARGER THAN
 THE WINDOW AND DOOR SIZES. THE REQUIRED PRESSURES FOR
 THE SLIDING GLASS DOOR SHOULD BE +33.9, -42.8 PSF. THE
 SIZE OF THE DOOR IN THE SCHEDULE DOES NOT MATCH THE
 ELEVATIONS. THE REQUIRED PRESSURES FOR THE WINDOWS
 SHOULD BE +37.9, -50.7 PSF FOR WALL ZONE 5 AND +37.9,
 -41.1 PSF FOR WALL ZONE 4. LOOK IN THE PRODUCT APPROVAL
 NOAS FOR THE APPROVED DESIGN PRESSURES FOR THE WINDOWS
 AND DOOR. THE OLD OUTDATED NOA NUMBERS WERE NOT REMOVED
 FROM THE SCHEDULES.
  
  