Plan Review Notes
Plan Review Notes For Permit 17080743
Permit Number 17080743
Review Stop M
Sequence Number 3
Notes
Date Text
2018-05-18 09:50:18PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) THIS PROJECT IS PERMITTED UNDER THE 2014 FBC. THE
 R405 ENERGY FORM THAT WAS SUBMITTED IS FOR THE 2017
 FBC. SUBMIT TWO SETS OF THE R405-2014 ENERGY FORMS.
  
 3) THE ENERGY FORMS R405-2014 ARE REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION
 R103.1.1.2.
  
 4) THE ATTIC VENT RATIO IS LISTED AS 300 SQFT ON THE
 ENERGY FORMS. FBC-R 806.2 THE MINIMUM NET FREE
 VENTILATION AREA SHALL BE 1/150 OF THE VENTED SPACE.
 THE EXCEPTION THAT ALLOWS THE 1/300 NET VENTILATION
 REQUIRES THAT AT LEAST 40 PERCENT AND NOT MORE THAN 50
 PERCENT OF THE REQUIRED VENTILATING AREA IS PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC
 OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NO
 MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST
 POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF
 FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF
 UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914
 MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL
 BE PERMITTED. THE PLANS DO NOT SHOW
  
 5) COMPLIED.
  