2018-05-18 09:07:53PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) ON SHEET A3.0 THE ROOFING MATERIAL IS SPECIFIED AS
 ASPHALT TILE ROOF ON A 90# HOT MOPPED TO A 30# BASE
 SHEET. PLEASE CLARIFY. FBC 107.2.1 WILL ASPHALT
 SHINGLES OR CONCRETE ROOF TILE BE INSTALLED? HOT MOPPED
 90# IS NOT USED AS AN UNDERLAYMENT FOR ASPHALT
 SHINGLES.
  
 4) THE PRODUCT APPROVAL NUMBERS THAT ARE SPECIFIED ON
 THE PLANS FOR THE WINDOWS IN THE SCHEDULE ON SHEET A4.0
 AND THE TRUSS CONNECTORS ON SHEET S2.0 ARE EXPIRED.
 PLEASE REMOVE FROM PLANS OR UPDATE THEM.
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL
 MULLIONS, SKYLIGHTS AND EXTERIOR DOOR TYPES.
  
 6) COMPLIED.
  
 10) COMPLIED.
  
 11) THE VALUATION LISTED ON THE PERMIT APPLICATION OF
 $12,000.00 IS LOW. PLEASE PROVIDE AN ADEQUATE VALUATION
 BASED ON FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. SUBMIT
 A COPY OF THE SIGNED CONTRACT FOR THIS PROJECT.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 13) NEW COMMENT: A PRODUCT APPROVAL WAS SUBMITTED FOR A
 SR PRODUCTS BUILT-UP ROOF SYSTEM OVER RECOVER DECKS.
 THIS PRODUCT WILL NOT WORK FOR THIS PROJECT. THIS IS
 FOR A ROOF OVER OR A RECOVER. THE MAXIMUM DESIGN
 PRESSURES ARE -45 PSF WHICH ARE TOO LOW AND LIMITATION
 #9 DOES NOT ALLOW THE PRESSURES TO BE INCREASED USING
 RATIONAL ANALYSIS OR EXTRAPOLATION
  