| 2018-03-29 16:24:44 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL |
| | PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS |
| | PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. THE MANUAL |
| | J EQUIPMENT SIZING CALCULATIONS THAT WERE SUBMITTED |
| | SPECIFY A 12000 BTUH PTAC UNIT. SHOW IT'S LOCATION ON |
| | THE PLANS AND PROVIDE AN EQUIPMENT SCHEDULE FRO IT. |
| | NOTE: FBC-R 303.9 REQUIRES THE ADDITION TO BE HEATED. |
| | |
| | 2) THIS PROJECT IS PERMITTED UNDER THE 2014 FBC. THE |
| | R405 ENERGY FORM THAT WAS SUBMITTED IS FOR THE 2017 |
| | FBC. SUBMIT TWO SETS OF THE R405-2014 ENERGY FORMS. |
| | |
| | 3) THE ENERGY FORMS R405-2014 ARE REQUIRED TO BE SIGNED |
| | BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION |
| | R103.1.1.2. |
| | |
| | 4) THE ATTIC VENT RATIO IS LISTED AS 300 SQFT ON THE |
| | ENERGY FORMS. FBC-R 806.2 THE MINIMUM NET FREE |
| | VENTILATION AREA SHALL BE 1/150 OF THE VENTED SPACE. |
| | THE EXCEPTION THAT ALLOWS THE 1/300 NET VENTILATION |
| | REQUIRES THAT AT LEAST 40 PERCENT AND NOT MORE THAN 50 |
| | PERCENT OF THE REQUIRED VENTILATING AREA IS PROVIDED BY |
| | VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC |
| | OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NO |
| | MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST |
| | POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE |
| | BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR |
| | CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF |
| | FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF |
| | UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914 |
| | MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL |
| | BE PERMITTED. THE PLANS DO NOT SHOW |
| | |
| | 5) FBC-R - M1401.3 SIZING. HEATING AND COOLING |
| | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS |
| | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER |
| | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. |
| | PROVIDE EQUIPMENT SIZING CALCULATIONS. |
| | |