| Plan Review Notes For Permit 17080743 |
| Permit Number |
17080743 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-07 14:48:41 | 9/7/17 1ST REVIEW PLUMBING DENIED | | | | | | 1) PLANS LIST BUILDING CODE AS 2010. WE ARE CURRENTLY | | | UNDER THE 2014 FIFTH EDITION FBC | | | | | | 2) P1 SHOWS A 2 HANDLE SHOWER VALVE. FBC-PLB 424.3 | | | REQUIRES SHOWER VALVES TO BE PRESSURE BALANCED, | | | THERMOSTATIC, OR A COMBINATION OF BOTH | | | | | | 3) SHOWER COMPARTMENTS PER FBC-PLB REQUIRE A MIN OF 900 | | | SQ IN. PLEASE SHOW SHOWER DIMENSIONS | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|