Plan Review Notes
Plan Review Notes For Permit 17080711
Permit Number 17080711
Review Stop G
Sequence Number 3
Notes
Date Text
2017-10-05 12:49:3310/5/17 3RD GAS REVIEW**DENIED**
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE INCLUDING EXIST
 SYTEM PER 2014 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR
 2014 FBC-RES SEC. G2413
  
 2) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE FOR BOTH REGULATORS USED. COMPLY WITH 2014
 FBC-FUEL GAS TABLE 402.4 (28) FOR THE PROPER PIPE SIZE
 AND BTU LOAD
  
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM.YOU ONLY INCLUDED THE P.E
 CHART (22) BUT YOU MUST INCLUDE ALL CHARTS FOR ALL PIPE
 TYPES AND PREESURES USED IN THE NEW AND EXISTING SYSTEM
 REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4, 401.8 THRU
 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR 2014
 FBC-RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
  
 4) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE NEW AND EXISTING. WPB AMENDMENTS TO FBC
 SEC.107.2.1.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION YOU PROVIDED SPECS FOR L.P LISTED AND
 APPROVED REGUALTORS WHILE YOUR SYSTEM IS NAT. 2014 FGC
 SEC.410.1
  