2017-09-01 18:23:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE STRUCTURE AND GENERATOR ARE LOCATED WITHIN 600
 FEET OF THE INTRACOASTAL WATERWAY. BASED ON
 FBC-R301.2.1.4.3, THE GENERATOR IS LOCATED IN EXPOSURE
 'D'. THE REQUIRED DESIGN PRESSURE FOR THE GENERATOR ON
 THE DOCUMENTS THAT WERE SUBMITTED IS 50 PSF. THE
 ALLOWABLE PRESSURE ON THE DOCUMENTS FOR THE PAD ARE
 39.20 PSF, WHICH DOES NOT MEET THE REQUIRED WIND LOADS.
 FBC-R301.2.1
  
 2) THE TWO SETS OF SITE SPECIFIC DESIGN PRESSURE
 REQUIREMENTS FOR THIS PROJECT AS REQUIRED BY GENERAL
 NOTE #2 ON THE GENERATOR PAD DRAWINGS THAT WERE
 SUBMITTED ARE FROM A FLORIDA LICENSED ENGINEER AND ARE
 REQUIRED TO BE SEALED AND HAVE THE ENGINEER'S
 HANDWRITTEN SIGNATURE. FAC 61G15 - 23.002
  
 3) IN ORDER TO MEET WIND LOAD REQUIREMENTS THE CONCRETE
 PAD HAS A MINIMUM WEIGHT REQUIREMENT FOR THE GENERATOR.
 SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS FOR
 THE GENERATOR THAT SPECIFY THE WEIGHT OF IT. FBC
 107.2.1
  