2017-08-23 14:32:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS.
  
 2) SUBMIT TWO SETS OF THE JOB SITE SPECIFIC DESIGN
 PRESSURES FOR THIS PROJECT AS REQUIRED BY GENERAL NOTE
 #2 ON THE GENERATOR PAD DRAWINGS. FBC 107.2.1
  
 3) IN ORDER TO MEET WIND LOAD REQUIREMENTS THE CONCRETE
 PAD HAS A MINIMUM WEIGHT REQUIREMENT FOR THE GENERATOR.
 SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS FOR
 THE GENERATOR THAT SPECIFY THE WEIGHT OF IT. FBC
 107.2.1
  
  
  