| Plan Review Notes For Permit 17080711 |
| Permit Number |
17080711 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-23 14:32:08 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE | | | FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN | | | SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT | | | ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE | | | ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS | | | AND DOCUMENTS. | | | | | | 2) SUBMIT TWO SETS OF THE JOB SITE SPECIFIC DESIGN | | | PRESSURES FOR THIS PROJECT AS REQUIRED BY GENERAL NOTE | | | #2 ON THE GENERATOR PAD DRAWINGS. FBC 107.2.1 | | | | | | 3) IN ORDER TO MEET WIND LOAD REQUIREMENTS THE CONCRETE | | | PAD HAS A MINIMUM WEIGHT REQUIREMENT FOR THE GENERATOR. | | | SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS FOR | | | THE GENERATOR THAT SPECIFY THE WEIGHT OF IT. FBC | | | 107.2.1 | | | | | | | | | |
|