Plan Review Notes
Plan Review Notes For Permit 17080703
Permit Number 17080703
Review Stop B
Sequence Number 2
Notes
Date Text
2017-08-29 12:26:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, SEE PREVIOUS LIST, SHEET GN-1D NOTES STATE
 THAT SCOPE IS INTERIOR DEMO, REVISE.
  
 2. FBC 107, SHEETS WERE REPLACED (A101, A102 AND
 OTHERS). THE FIRST VERSION HAD NO FLOOR PLAN AND SHOWED
 ONLY THE SCOPE PROPOSED (WINDOW REPLACEMENT). THE NEW
 PAGES INCLUDE FLOOR PLANS AND WALL SPECIFICATIONS.
 PLEASE REFER TO THE PREVIOUS COMMENT LIST AND MODIFY
 PAGES TO ADDRESS COMMENTS ONLY. FLOOR PLANS SHOULD NOT
 BE INCLUDED IN A WINDOW REPLACEMENT PERMIT AS THAT IS
 BEYOND THE SCOPE OF THIS REVIEW AND SCOPE OF THIS
 PERMIT APPLICATION.
  
 THE WORK PROPOSED (REMOVAL OF MASONRY WALLS, INFILL
 DETAIL, WINDOW REPLACEMENT) IS NO LONGER ON THE PLANS.
 PROJECT NAME IS "THE FORUM HOTEL - RENOVATION WINDOW
 REPLACEMENT". REVISE TO STATE "WINDOW REPLACEMENT" AND
 REVISE PLAN TO RESTORE THE INFORMATION DESCRIBING SCOPE
 WHICH WAS PREVIOUSLY REVIEWED (VERSION 1).
  
 VERSION 2 INCLUDES THE WINDOW LOCATIONS. PLEASE REVISE
 VERSION 1 TO INCLUDE THIS INFORMATION. OR, REVISE
 VERSION 2 TO REMOVE THE FLOOR PLANS AND ADD THE
 INFORMATION FROM VERSION 1.
  
 3. THE APPLICATION DOES NOT INCLUDE DOOR INSTALLATION.
 SEE WINDOW TYPE D; IT IS NOT CLEAR HOW YOU WILL
 ACCOMPLISH THIS INSTALLATION WITHOUT A DOOR. IS THIS A
 PART OF THE SCOPE? EITHER REMOVE FROM SCOPE OR CLARIFY.
 IF DOORS ARE PROPOSED IN THE SCOPE OF THIS PERMIT, A
 PRODUCT APPROVAL IS REQUIRED. WILL DOOR D INCLUDE PANIC
 HARDWARE (APPEARS TO BE REQUIRED, ASSEMBLY OCCUPANCY)?
 IF NOT, A LIFE SAFETY PLAN AND FIRE REVIEW WILL BE
 REQUIRED.
  
 4. THE NOA UPLOADED IS INCOMPLETE. FBC 107, PROVIDE A
 COMPLETE DOCUMENT. IT APPEARS THAT THE LARGE DRAWING
 PAGES WERE PRINTED ON 8 1/2 X 11 PAPER (BUT REQUIRED 11
 X 17 OR CHANGE OF ORIENTATION), SO THE RIGHT HALF OF
 THE PAGE IS MISSING.
  
 5. REVISE PLAN TO SHOW PROPOSED LOCATIONS OF WINDOWS
 SHOWN IN THE SCHEDULE ON A602.
  
 6. IT IS NOT CLEAR WHERE WINDOW E IS IN THE PRODUCT
 APPROVAL, PLEASE DIRECT. SHEET 4 OF 11 ON THE PRODUCT
 APPROVAL APPEARS TO SHOW A LIMIT OF 60" X 120" AND
 APPEARS TO HAVE ONE MULLION. WINDOW E IS 6'6" X 9'8"
 WITH A 2" LINE WHICH APPEARS TO BE A MULLION. REVISE
 PLAN AND MARK UP PRODUCT APPROVAL TO CLARIFY COMPLIANCE
 OF PROPOSED INSTALLATION.
  
 7. WINDOW B, A STRUCTURAL MULLION IS PROPOSED. PROVIDE
 THE PRODUCT APPROVAL, FBC B 1609.
  
 8. THE WINDOW LOCATION INFORMATION IS ON VERSION 2 OF
 THE FLOOR PLANS. PLEASE REVISE VERSION 1 PLAN TO
 INCLUDE THIS INFORMATION.
  
 9. PERMIT APPLICATION DESCRIPTION NOT CLEAR. IT STATES:
 "INSTALLATION OF REPLACEMENT WINDOWS IN PLACE OF
 EXISTING WINDOWS REMOVED AS PART OF DEMOLITION." WINDOW
 REMOVAL IS NOT INCLUDED IN THE SCOPE OF THE DEMO
 PERMIT. WINDOW REMOVAL WILL BE INCLUDED IN THE SCOPE OF
 THIS PERMIT. PROVIDE A CORRECTED APPLICATION.
  
  
  