| 2017-08-29 12:26:04 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. FBC 107, SEE PREVIOUS LIST, SHEET GN-1D NOTES STATE |
| | THAT SCOPE IS INTERIOR DEMO, REVISE. |
| | |
| | 2. FBC 107, SHEETS WERE REPLACED (A101, A102 AND |
| | OTHERS). THE FIRST VERSION HAD NO FLOOR PLAN AND SHOWED |
| | ONLY THE SCOPE PROPOSED (WINDOW REPLACEMENT). THE NEW |
| | PAGES INCLUDE FLOOR PLANS AND WALL SPECIFICATIONS. |
| | PLEASE REFER TO THE PREVIOUS COMMENT LIST AND MODIFY |
| | PAGES TO ADDRESS COMMENTS ONLY. FLOOR PLANS SHOULD NOT |
| | BE INCLUDED IN A WINDOW REPLACEMENT PERMIT AS THAT IS |
| | BEYOND THE SCOPE OF THIS REVIEW AND SCOPE OF THIS |
| | PERMIT APPLICATION. |
| | |
| | THE WORK PROPOSED (REMOVAL OF MASONRY WALLS, INFILL |
| | DETAIL, WINDOW REPLACEMENT) IS NO LONGER ON THE PLANS. |
| | PROJECT NAME IS "THE FORUM HOTEL - RENOVATION WINDOW |
| | REPLACEMENT". REVISE TO STATE "WINDOW REPLACEMENT" AND |
| | REVISE PLAN TO RESTORE THE INFORMATION DESCRIBING SCOPE |
| | WHICH WAS PREVIOUSLY REVIEWED (VERSION 1). |
| | |
| | VERSION 2 INCLUDES THE WINDOW LOCATIONS. PLEASE REVISE |
| | VERSION 1 TO INCLUDE THIS INFORMATION. OR, REVISE |
| | VERSION 2 TO REMOVE THE FLOOR PLANS AND ADD THE |
| | INFORMATION FROM VERSION 1. |
| | |
| | 3. THE APPLICATION DOES NOT INCLUDE DOOR INSTALLATION. |
| | SEE WINDOW TYPE D; IT IS NOT CLEAR HOW YOU WILL |
| | ACCOMPLISH THIS INSTALLATION WITHOUT A DOOR. IS THIS A |
| | PART OF THE SCOPE? EITHER REMOVE FROM SCOPE OR CLARIFY. |
| | IF DOORS ARE PROPOSED IN THE SCOPE OF THIS PERMIT, A |
| | PRODUCT APPROVAL IS REQUIRED. WILL DOOR D INCLUDE PANIC |
| | HARDWARE (APPEARS TO BE REQUIRED, ASSEMBLY OCCUPANCY)? |
| | IF NOT, A LIFE SAFETY PLAN AND FIRE REVIEW WILL BE |
| | REQUIRED. |
| | |
| | 4. THE NOA UPLOADED IS INCOMPLETE. FBC 107, PROVIDE A |
| | COMPLETE DOCUMENT. IT APPEARS THAT THE LARGE DRAWING |
| | PAGES WERE PRINTED ON 8 1/2 X 11 PAPER (BUT REQUIRED 11 |
| | X 17 OR CHANGE OF ORIENTATION), SO THE RIGHT HALF OF |
| | THE PAGE IS MISSING. |
| | |
| | 5. REVISE PLAN TO SHOW PROPOSED LOCATIONS OF WINDOWS |
| | SHOWN IN THE SCHEDULE ON A602. |
| | |
| | 6. IT IS NOT CLEAR WHERE WINDOW E IS IN THE PRODUCT |
| | APPROVAL, PLEASE DIRECT. SHEET 4 OF 11 ON THE PRODUCT |
| | APPROVAL APPEARS TO SHOW A LIMIT OF 60" X 120" AND |
| | APPEARS TO HAVE ONE MULLION. WINDOW E IS 6'6" X 9'8" |
| | WITH A 2" LINE WHICH APPEARS TO BE A MULLION. REVISE |
| | PLAN AND MARK UP PRODUCT APPROVAL TO CLARIFY COMPLIANCE |
| | OF PROPOSED INSTALLATION. |
| | |
| | 7. WINDOW B, A STRUCTURAL MULLION IS PROPOSED. PROVIDE |
| | THE PRODUCT APPROVAL, FBC B 1609. |
| | |
| | 8. THE WINDOW LOCATION INFORMATION IS ON VERSION 2 OF |
| | THE FLOOR PLANS. PLEASE REVISE VERSION 1 PLAN TO |
| | INCLUDE THIS INFORMATION. |
| | |
| | 9. PERMIT APPLICATION DESCRIPTION NOT CLEAR. IT STATES: |
| | "INSTALLATION OF REPLACEMENT WINDOWS IN PLACE OF |
| | EXISTING WINDOWS REMOVED AS PART OF DEMOLITION." WINDOW |
| | REMOVAL IS NOT INCLUDED IN THE SCOPE OF THE DEMO |
| | PERMIT. WINDOW REMOVAL WILL BE INCLUDED IN THE SCOPE OF |
| | THIS PERMIT. PROVIDE A CORRECTED APPLICATION. |
| | |
| | |
| | |