| Date |
Text |
| 2017-08-17 07:02:26 | ***CORRECTIONS*** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. GN-1 DIVISISION 1 GENERAL REQUIREMENTS (AND ANY |
| | OTHER LOCATIONS IF APPLICABLE), REVISE PLAN TO REMOVE |
| | REFERENCE TO MARTIN COUNTY, FBC 107. |
| | |
| | 2. BUILDING CODE SUMMARY, REVISE SCOPE OF WORK |
| | (CURRENTLY STATES INTERIOR DEMOLITION). REMOVE |
| | REFERENCE TO MARTIN COUNTY. |
| | |
| | 3. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC B |
| | 1603.1.4. |
| | |
| | 4. REVISE PLAN TO INCLUDE A WINDOW SCHEDULE, FBC B |
| | 1609. THE WINDOWS PROPOSED MUST EITHER MEET THE SIZE |
| | LIMITATIONS IN THE PRODUCT APPROVAL OR SITE SPECIFIC |
| | ENGINEERING REQUIRED. |
| | |
| | 5. OK |
| | |
| | 6. PLANS STATE TO INSTALL GLAZING AND MASONRY INFILL |
| | "TO THE EXTENTS INDICATED". WHILE HORIZONTAL DIMENSIONS |
| | ARE PROVIDED, VERTICAL DIMENSIONS DO NOT APPEAR TO BE |
| | PROVIDED. IT APPEARS THAT IT IS POSSIBLE THAT SOME |
| | PAGES WERE INADVERTENTLY NOT SUBMITTED. PROVIDE EITHER |
| | ELEVATIONS WITH REQUIRED INFORMATION (SEE FBC 107, |
| | PLANS TO SHOW SCOPE AND NATURE OF PROPOSED WORK), OR A |
| | SCHEDULE, OR ANY OTHER OPTION WHICH CLEARLY SHOWS |
| | WINDOW SIZES. IF ALL WINDOWS ARE THE SAME HEIGHT, A |
| | NOTE WILL SUFFICE. IF A NOTE IS USED, PLEASE PUT IN A |
| | VISIBLE LOCATION (NOT BURIED IN GENERAL NOTES). |
| | |
| | 7. FBC EC TABLE C402.3, PROVIDE SPEC SHEETS WHICH SHOW |
| | U-FACTOR AND SHGC FOR THE PROPOSED WINDOWS, OR REVISE |
| | THE SIGNED AND SEALED PLAN TO INCLUDE THIS INFORMATION. |
| | |
| | 8. IT IS NOT CLEAR WHETHER THIS ASPECT OF THE PROJECT |
| | WILL COMPLY WITH FBC ENERGY CONSERVATION. PLEASE SEE |
| | FBC EB CHAPTER 2, DEFINITION OF "RENOVATED BUILDING". |
| | ENERGY CALCS WILL BE REQUIRED FOR THE INTERIOR BUILDOUT |
| | PERMIT. |
| | |
| | IT IS UNDERSTOOD THAT THE INTERIOR IS STILL IN DESIGN |
| | PHASE. PLEASE CONFIRM, VIA A SIGNED AND SEALED RESPONSE |
| | LETTER, THAT APPLICANT HAS RESEARCHED THIS ISSUE AND |
| | CONFIRMS THAT PROPOSED WINDOWS WILL NOT AFFECT |
| | APPLICANT'S ABILITY TO DESIGN A BUILDOUT WHICH COMPLIES |
| | WITH FBC ENERGY CONSERVATION REQUIREMENTS. ALSO |
| | ACKNOWLEDGE THAT APPLICANT PROCEEDS AT APPLICANT'S OWN |
| | RISK. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |