| Plan Review Notes For Permit 17080682 |
| Permit Number |
17080682 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-11-29 06:01:11 | 1) AN AIR ADMITTANCE VALVE CANNOT BE USED TO VENT THE | | | ADDED BATHROOM GROUP. THE VENT SYSTEM SERVING EACH | | | BUILDING DRAIN SHALL HAVE AT LEAST ONE VENT PIPE THAT | | | EXTENDS TO THE OUTDOORS. FBCR SEC.P3102.1. | | | 2) SHT. A3 NOTES THAT ALL PLUMBING LINES SHALL SLOPE A | | | MINIMUM OF 1/8 INCH PER FOOT. PIPING 2 1/2 INCHES OR | | | LESS SHALL BE SLOPED A MINIMUM OF 1/4 INCH PER FOOT PER | | | FBCR SEC.P3005.4.2. | | | 3) THE WATER SUPPLY VALVES FOR THE STACKABLE WASHER AND | | | DDRYER SHALL BE ACCESSIBLE. FBCR SEC.P2903.9.3. | | | 4) THE SANITARY RISER SUPPLIED BY THE PLUMBING | | | CONTRACTOR NOTES CORE DRILLING THROUGH THE FOOTER. SHOW | | | THE SIZE OF THE DRILLED OPENING. TWO COPIES OF A SIGNED | | | AND SEALED LETTER FROM THE ARCHITECT OF RECORD SHALL BE | | | SUBMITTED VERIFYING THAT THE CORE DRILLING OF THE | | | FOOTING WILL NOT COMPROMISE THE STRUCTURAL INTEGRITY OF | | | THE FOOTING FOR HANDLING ALL IMPOSED LOADS.FBCR SEC. | | | R301, FBCR SEC. R403.1. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|