| 2018-10-31 16:01:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2012 |
| | 5TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 3RD REVIEW: |
| | GAS PIPING COMMENTS: DENIED |
| | |
| | 1. RE: WPB FBC 107.2.1; MANUFACTURER?S SPECIFICATION |
| | SHEETS REQUIRED SUBMITTALS |
| | A) NG LINE REGULATOR (MP) |
| | ? PROVIDE ONE SPEC SHEET TO ACCOMPANY EACH APPLIANCE |
| | INCLUSIVE OF EXISTING POOL HEATER, NOTING INDOOR OR |
| | OUTDOOR APPLICATION AND SPECIFY CORRECT VENT LIMITING |
| | DEVICE OR VENT PROTECTOR AS REQUIRED BY APPLICATION. |
| | B) TANKLESS WATER HEATER |
| | ? RINNAI RL75E IS NOT FOR INDOOR INSTALLATION |
| | 1) SUBMIT A UNIT FOR INDOOR USE |
| | 2) PROVIDE DETAIL AND MANUFACTURER?S RECOMMENDED VENT |
| | TERMINATION KIT SPEC |
| | 3) IDENTIFY RUSKIN LOUVER AS 12 X 18 COMBUSTION AIR |
| | VENT |
| | 4) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY |
| | APPLICATION |
| | C) BBQ GRILL |
| | ? SALES BROCHURE IS NOT ADEQUATE |
| | 1) PROVIDE MANUFACTURER?S SPEC SHEET FOR UNIT. |
| | 2) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY |
| | APPLICATION |
| | D) EXISTING EQUIPMENT |
| | ? POOL HEATER |
| | 1) PROVIDE MANUFACTURER?S SPEC SHEET FOR UNIT. |
| | 2) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY |
| | APPLICATION |
| | 2. REVISE THE GAS PIPING RISER DIAGRAM THAT SHOWS THE |
| | TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE INCLUSIVE OF THE EXISTING POOL HEATER, THE |
| | RUN FROM THE NEW APPLIANCES BACK TO THE INTERSECTION |
| | WITH THE BRANCH TO THE EXISTING POOL HEATER, THE RUN |
| | FROM THAT INTERSECTION TO THE UPGRADED REGULATOR AND |
| | METER AND THE DISTANCE OF THE LONGEST LENGTH OF PIPING |
| | FROM THE POINT OF DELIVERY TO THE MOST REMOTE OUTLET |
| | INCLUSIVE OF THE EXISTING POOL HEATER AND THE LOAD OF |
| | THE SECTION. |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| | ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |
| | ADDITIONAL NOTES; DOES NOT APPLY TO PERMIT APPLICATION |
| | |
| | 1. CITY RECORDS SHOW .5LB GAS ON EXISTING SYSTEM. |
| | PROVIDE AFFIDAVIT OF GAS PIPING TEST TO INCLUDE OF |
| | EXISTING SYSTEM FOR FINAL INSPECTION IN ACCORDANCE WITH |
| | FBC FG 406 TO INSURE IT IS 2PSI CAPABLE. |
| | 2. THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES / |
| | EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION. |
| | FGC SEC.305.1, FBC-RES. |
| | |