| 2018-02-09 15:06:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. SEE NEW |
| | COMMENT THAT FOLLOWS THE ORIGINAL COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. PROVIDE SPEC SHEET FOR EXISTING METER CAN SHOWING |
| | DOUBLE LUG COMPATIBLE. DESCRIBE METHOD OF DOUBLE LUG |
| | TAP. FBC 107.2.1, NEC 110.3 (PLAN SHOWS A TAP FROM THE |
| | 200 AMP DISCONNECT TO BE INSTALLED. WHAT IS THE METHOD |
| | OF THIS TAP? MOST 200 AMP DISCONNECTS HAVE A LUG RATED |
| | FOR A SINGLE WIRE, NOT FOR TWO AS SHOWN IN RISER. |
| | PROVIDE CLARIFICATION AND/OR CORRECT.) |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER FOR PANEL A AT THE NEW BUILDING. NEC |
| | 225.31, 225.32 (THE MOUNTING LOCATION OF THE DISCONNECT |
| | THAT WAS ADDED FOR THIS IS NOT SHOWN ON POWER PLAN. |
| | SHOW LOCATION OF DISCONNECT SO RISER AND POWER PLAN |
| | MATCH. FBC 107.2.1) |
| | 9. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| | RE3607.3 (NOTE ON PLAN STATES THIS IS NOT REQUIRED PER |
| | FIGURE 250.87, WHICH DOES NOT EXIST. THIS IS REQUIRED, |
| | PROVIDE AS PREVIOUSLY REQUESTED. SEE EXHIBIT 250.19 IN |
| | THE NEC HANDBOOK FOR FURTHER CLARIFICATION.) |
| | 10. CORRECTED. |
| | 11. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| | LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| | FBC RE3903.3 (A SWITCH SHOULD BE LOCATED AT EACH GRADE |
| | LEVEL ACCESS, ONE IS MISSING.) |
| | 12. CORRECTED. |
| | |
| | NEW COMMENT: |
| | |
| | 13. PLEASE BE ADVISED THAT SOME COMMENTS HAVE NOT BEEN |
| | ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF |
| | IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD |
| | TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS |
| | REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |