| 2017-08-29 15:24:11 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE # 1 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE4002.14 |
| | 2. NOTE # 11 STATES THAT LIGHTING IN CLOTHES CLOSETS |
| | SHALL COMPLY WITH NEC 4/10.8/D/1, WHICH DOESN?T EXIST. |
| | PROVIDE CORRECTION. NEC 410.16; FBC RE4003.12 |
| | 3. SEVERAL ELECTRICAL NOTES REFER TO EXISTING |
| | INSTALLATION, BUT THE PERMIT APPLICATION STATES THIS IS |
| | A NEW BUILDING. REMOVE ANY NOTES NOT PERTAINING TO THIS |
| | JOB. FBC 107.2.1 |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 5. PROVIDE SPEC SHEET FOR EXISTING METER CAN SHOWING |
| | DOUBLE LUG COMPATIBLE. DESCRIBE METHOD OF DOUBLE LUG |
| | TAP. FBC 107.2.1, NEC 110.3 |
| | 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 |
| | 7. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, LOCATION OF MAIN DISCONNECTS AND |
| | LABELING FOR THOSE DISCONNECTS, UNDERGROUND OR OVERHEAD |
| | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| | INTERIOR PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1, |
| | RE3609.3; FBC 107.2.1 |
| | 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER FOR PANEL A AT THE NEW BUILDING. NEC |
| | 225.31, 225.32 |
| | 9. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| | RE3607.3 |
| | 10. ADDRESS PANEL A LOCATION. OVERCURRENT PROTECTION |
| | DEVICES ARE NOT PERMITTED IN THE VICINITY OF EASILY |
| | IGNITABLE MATERIAL, SUCH AS IN CLOTHES CLOSETS. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. NEC 240.24(D); FBC |
| | RE3705.7 |
| | 11. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| | LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| | FBC RE3903.3 |
| | 12. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC CE R404.1 |
| | |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |