2017-12-01 12:28:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE ARE ELECTRICAL SHEETS,E1, E2, E3, ATTACHED AT
 REAR OF PLAN THAT ARE NOT SIGNED/SEALED. THERE ARE ALSO
 OTHER SHEETS FOR OTHER DISCIPLINES THAT ARE NOT
 SIGNED/SEALED. PER THE WPB AMENDMENTS TO THE FBC, PLAN
 IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE
 CORRECTION. FBC 107.2.1, FS 471, 481
 2. PANEL SCHEDULE SHOWS A 120 AMP BREAKER FOR THE X-RAY
 MACHINE. THIS IS NOT A STANDARD SIZE FOR BREAKERS. IS
 THIS POSSIBLY A TYPO? OR WILL THIS BE A SPECIAL ORDER
 BREAKER. IF SO, PROVIDE SPEC SHEET. PLEASE CLARIFY
 AND/OR CORRECT. NEC 110.3; FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  